How to Configure Individual Events

Event List page

The Actions option in the Events menu opens the “Event Action Configuration” page on the Web interface. Use the Details button in this page to access a complete list of the events that can be reported by your Switched Rack PDU.

Modifying events on the Configure Event Action by Severity Level page will override any changes you have made to individual events on the Details page.

Each event is identified by its unique code, its description, and its assigned severity level. For example:

Code

Description

Severity

 

 

 

0x0002

System: Warmstart.

Severe

 

 

 

0x0F0A

Switched Rack PDU: Low load threshold exceeded

Warning

 

 

 

For information about severity levels and how they define the actions associated with events, see Event Actions (Web Interface Only).

Detailed Event Action Configuration page

The event codes provide a link to a page that allows you to do the following:

Change the selected event’s severity level

Enable or disable whether the event uses the event log, Syslog messages, SNMP traps, or e-mail notifications