Switched Rack PDU
USER’S GUIDE
®
Switched Rack PDU Settings
Configure Load Thresholds
Web interface.
1.Select Switched Rack PDU from the navigation menu.
2.Click Configure in the Load Management section.
3.Set Overload Alarm Threshold, Near Overload Warning Threshold, Low Load Warning Threshold, and Overload Outlet Restrictions for each phase or bank.
4.Click Apply in that section to set the selected values.
Control console.
1.From the Device Manager menu, select Phase/Bank Monitor/ Configuration.
2.Select a phase or bank (for
3.Select Overload Alarm Threshold (amps), Near Overload Warning Threshold (amps), or Low Load Warning Threshold (amps).
4.Select Accept Changes.
To set the overload outlet restriction, select Outlet Restriction Configuration on the Device manager menu. For
Setting | Description |
|
|
Overload Alarm | Set the number of amps that will cause an overload of this phase |
Threshold | or bank. |
|
|
Near Overload | Set the number of amps at which to generate a warning that the |
Warning Threshold | Rack PDU is nearing overload of a phase or bank. |
|
|