Switched Rack PDU

USER’S GUIDE

®

Control actions you can select.

t

Option

Description

 

 

No Action (Web interface only)

Do nothing.

 

 

On Immediate

Apply power to the selected outlets.

 

 

On Delayed

Apply power to each selected outlet according to its

 

value for Power On Delay.

Off Immediate

Remove power from the selected outlets.

 

 

Off Delayed

Remove power from each selected outlet according to

 

its value for Power Off Delay.

Reboot Immediate

Remove power from each selected outlet. Then apply

 

power to each of these outlets according to its value

 

for Reboot Duration.

Reboot Delayed

Remove power from each selected outlet according to

 

its value for Power Off Delay. Wait until all outlets are

 

off (the highest value for Reboot Duration), and then

 

apply power to each outlet according to its value for

 

Power On Delay.

Cancel Pending Commands

Cancel all commands pending for the selected outlets

(Web Interface)

and keep them in their present state.

Cancel (control console)

NOTE: For global outlet groups, you can cancel a

 

command only from the interface of the initiator outlet

 

group. The action will cancel the command for the

 

initiator outlet group and all follower outlet groups.

 

 

† If a local outlet group is selected, only the configured delays and reboot duration of the lowest- numbered outlet of the group are used. If a global outlet group is selected, only the configured delays and reboot duration of the global outlet are used.