Outlet Settings for Outlets and Outlet Groups

How to initiate a control action

Web i nter face. To control the outlets on your Switched Rack PDU
1. Select Outlets, and then Control on the navigation menu.
2. Mark the check-boxes for each individual outlet or outlet g roup to
control, or select the All Outlets check-box.
3. Select a Control Action from the list, and click Next >>. On the
confirmation page that explains the action, choose to execute or cancel it.
Control Console. Select Outlet Control/Configuration from the Device
Manager menu to display a list of outlets. For each outlet, the list indicates
whether it is a member of an outlet group.
1. Choose either or the following:
– To control one outlet and the outlet group, if any, to which it belongs,
select the number of the outlet, and then select Control Outlet.
– To control all outlets, select Master Control/Configuration, and
then Control of ALL Outlets.
2. Select a control action.
3. On the confirmation screen that describes the action to b e executed,
type Yes at the prompt to perform the action.
If you apply an outlet control action to outlets or outlet groups, the
following delays are used for the action:
• For an individual outlet (not in an outlet group), the action uses
the delay periods and reboot duration configured for that outlet.
• For a global outlet group, the action uses the delay periods
and reboot duration configured for the global outlet.
• For a local outlet group, the action uses the delay periods
configured for the lowest-numbered outlet in the group.