Select the Baud Rate
Genius bus communications can occur at any of four baud rates: 153.6 Kbaud standard, 153.6 Kbaud extended, 76.8 Kbaud, or 38.4 Kbaud. The default is 153.6 K baud (standard). The Genius I/O System User's Manual gives guidelines for baud rate selection.
Each device's communications baud rate must be the same as that used by all other devices on the bus, or the bus will not operate.
HHM Display
SELECT BAUD RATE ACTIVE=153.6K ST PROG =153.6K ST tgl entr nxt
Configuration Steps
1.If the baud rate should be changed, press F2 (toggle). When the desired baud rate
appears beside P R O G = , press F3 (enter).
2.If the baud rate is changed on any block that is currently installed on an operating bus, it must be changed on all devices on that bus. After changing the baud rate, you must cycle power at the same time to all devices on the bus to use the new baud rate.
3.Press F4 (nxt) to continue configuring the Remote I/O Scanner.