Section 1: Introduction 1-5

70055MP Revision D February 3, 2000

Electrical
Sensor Power Supply 24 VDC @ 0.65A.
Power Input
Protection Fused (F1)
Type: AGC3 instant blow.
Rating: 3A @ 250 V.
Power Input
(Electrical Rating) AC: Standard: 120 VAC +10/-15%AC, 50 - 60 Hz.
Optional (factory set): 240 VAC +10/-15%AC, 50 - 60 Hz.
DC: 125 VDC +15%DC.
NOTE: Monitors supplied with internal heater option must
have AC power input.
Power Consumption Less than 16VA.
Supply Voltage
Fluctuation Mains supply voltage must not exceed +10% of nominal
supply voltage.
Environmental
Operating
Temperature Range Standard: 0°C to +60 °C (+32°F to +140 °F).
With Heater Option: -40°C to +60 °C (-40°F to +140 °F).
Pollution Degree 4.
Maximum Relative
Humidity 80%.
Maximum Altitude 2000m.
Physical Enclosure
Material Stainless steel, weather-proof.
Standard NEMA Type 4.
Dimensions 12” (305 mm) x 12” (305 mm) x 6” (152 mm).
Weight 18 lbs. (8.16 kg); additional weight for accessories.

NOTE: Specifications subject to change without notice.