4-2 Section 4: Operation
February 3, 2000 70055MP Revision D
Analog Channel Readings Screens The Analog Channel Readings screens display up to four channels each
(see Figure 4-1). There is one line of display (20 columns) available for each
channel:
• Columns 1 through 10 display the channel’s description as uploaded
from the SAGE configuration file.
• Columns 11through 16 display a numeric representation of the current
value being read at the channels input.
• Columns 17 through 20 display the units of the reading.
• If a channel is not connected, no information is displayed for the
channel; down arrows indicate that pressing Operating Conditions will
display more information (e.g., other configured analog channel
readings, or digital channel readings).
R M
T E M
P 3 7 . 5 d e g C
T o p O i l 4 5 . 3 d e g C
â ââ â
L o a d C u r r e 6 8 9 A m p
Figure 4-1: Sample Analog Channel Display
Digital Channel Readings Screens The Digital Channel Readings screens display up to four channels each
(see Figure 4-2). There is one line of display (20 columns) available for each
channel:
• Columns 1 through 17 display the channel’s description as uploaded
from the SAGE configuration file.
• Columns 18 through 20 display the channels status as ON or OFF.
C N T R L I S O 1 C H 1 O N
C N T R L I S O 1 C H 2 O N
C N T R L I S O 1 C H 3 O N
C N T R L I S O 1 C H 4 O F F
Figure 4-2: Sample Digital Channel Display