Section 3: Installation 3-19
70055MP Revision D February 3, 2000
Wiring the Internal Heater The monitor’s internal heater requires 110 VAC power input. Refer to Figure
3-9 for Heater Terminal locations.
WARNING: Do not bridge the heater power terminals to the monitor power
supply terminals if DC is used to supply the monitor. The heater is AC only.
Wiring Power The LTC-MAP 2130 is factory configured for either 120 VAC or 240 VAC
operation per the customer order. Refer to Figure 3-9 for the location of the
Power Input Terminals.
1. Connect the “hot” phase of the 120 or 210 power line to the LINE Power
Input Terminal.
2. Connect the neutral line to the NEUT Power Input Terminal.