Section 3: Installation 3-23
70055MP Revision D February 3, 2000
Initial Start Up
1. Before applying power to the system, verify that:
All sensors are mounted and connected properly.
None of the wiring or cables are shorted.
All connections follow the wiring and installation diagrams.
All monitored input signals are within specified input ranges.
Phone lines are properly connected to a phone multiplexer (if used).
WARNING: Check all wiring before applying power to the unit. Wiring
errors can damage the device and create a safety hazard.
2. Connect the power input wires to the 120 V AC/DC Power terminal.
3. Apply power to the monitor.
NOTE: Copyright information will be displayed for approximately
ten seconds. After that, the display will go blank.
L T C - M
A P 2 1 3 0
r e v 2 1 3 0 . x x . y y
c o p y r I g h t ( C ) 1 9 9 7
4. Configure and set system parameters using the SAGE host software
package. (Refer to the SAGE documentation for specific
procedures.)
5. Upload the SAGE configuration files to the LTC-MAP, either through
the RS232 Serial port or via a modem. (Refer to the SAGE
documentation for specific procedures.)
6. Verify the current date and time.
Press the Alarm Status & Settings button two times or until the
Current Time and Current Date screen is displayed:
C u r r e n t T i m e :
1 2 : 3 0 : 2 2
C u r r e n t D a t e :
W
e d 0 9 / 1 7 / 1 9 9 7
If the time and date are incorrect, reset them using the procedures
outlined in the SAGE documentation.
NOTE: The date and time must be set accurately to insure that LTC-
MAP 2130 properly acquires data.