Generac 004912-0, 004912-1, 004913-0, 004913-1 owner manual Maintenance, Level

Models: 004912-0, 004912-1, 004913-0, 004913-1, 004913-2 004912-0, 004912-1, 004913-0, 004913-1

1 52
Download 52 pages 6.08 Kb
Page 24
Image 24
Maintenance

Section 4 — Maintenance

Centurion Liquid-cooled 15 kW and 25 kW Generators

Maintenance

Level 1

 

Level 2

 

Level 3

 

Level 4

 

Tasks

Recom-

Task

Required

Task

Required

Task

 

Task

 

mended

Comp.

to be done

Comp.

to be done

Comp.

Required

Comp.

 

to be done

(Date-

3 months/

(Date-

Semi-

(Date-

to be done

(Date-

 

monthly/

Initials)

Break-in

Initials)

annually/

Initials)

Annually/

Initials)

 

10 hrs.

 

30 hrs.

 

50 hrs.

 

100 hrs.

 

13.Initiate an automatic start and transfer of the unit to site load and exercise it for at least one hour looking

for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary.

14.Start and exercise the unit at full rated load (use a

load bank if the site load is not enough) for at least two hours looking for leaks, loose connections components, and abnormal operating conditions. Correct as necessary.

15. Change the engine oil.

16.Replace the engine oil filter(s).

17.Replace the engine air filter(s).

18.Check the engine spark plugs on gas engine driven units. Clean and re-gap or replace as necessary.

19.Perform a five minute no-load operational run of the unit looking for any post service problems.

20.Return the unit to standby

setup for operation when required.

22 Generac® Power Systems, Inc.

Page 24
Image 24
Generac 004912-0, 004912-1, 004913-0, 004913-1, 004913-2 owner manual Maintenance, Level