Section 1 - General Information
Centurion
1.1GENERATOR
This equipment is a
These models are available. They are rated as follows:
Model 004912 : Provides 15,000 watts (15 kW) of
Model 004913: Provides 25,000 watts (25 kW) of
If this generator is used to power electrical
!load circuits normally powered by a utility power source, it is required by code to install a transfer switch. The transfer switch must effectively isolate the electric system from the utility distribution system when the generator is operating (NEC 701). Failure to isolate an electrical system by such means results in damage to the generator and may also result in injury or even death to utility power workers due to backfeed of electrical energy.
1.3AUTOMATIC SYSTEM OPERATION
When this generator, along with its transfer switch, has been installed and interconnected, a circuit board in the generator panel constantly monitors utility power source voltage. Should that voltage drop below a preset value, and remain at such a low state for a preset amount of time, the generator cranks and starts. After the generator starts, the transfer switch transfers load circuits so the generator can power them.
When utility source voltage has been restored, the switch
Please reference the transfer switch manual for specific information.
1.4GENERATOR AC CONNECTION
SYSTEMS
The generator was shipped from the factory with its stator AC output leads connected in a
Figure 1.1 - Generator AC Connection System
1.2TRANSFER SWITCH
This generator system includes a matched automatic transfer switch which is intended to be used in conjunction with the Centurion generator. It is supplied in a NEMA 3R enclosure. The NEMA 3R enclosure is weather resistant and can be used indoors or outdoors. Follow these rules:
•Install the transfer switch on a firm, sturdy supporting structure.
•To prevent switch distortion, level the switch if necessary. This can be done by placing washers between the switch enclosure and the mounting surface.
•Never install the switch where water or any corrosive substance might drip onto the enclosure.
•Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and corrosive vapors.
•It is highly recommended to utilize a Generac/Centurion transfer switch with this generator or it may void the warranty.
NOTE:
Rated power of generator is subject to and limited by such factors as ambient temperature, altitude, engine condition, and other factors. Engine power will decrease about 3% for each 1000 feet above 3000 feet and will decrease an additional 1.5% for each 10°F above 77°F. Maximum output power of the generator is limited by maximum engine power.
4 Generac® Power Systems, Inc.