‹3.2.6 SYSTEM READY LED

Section 3 - Operation

Guardian Liquid-cooled 25 kW Generator

 

Condition

System

Low

Low

High

Over

 

Over

Switch Position

 

 

 

Ready (Green)

Bat (Red)

Oil (Red)

Temp (Red)

Speed (Red)

 

Crank (Red)

Manual

Auto

Off

 

 

Generator Switch is

OFF

X

OFF

OFF

OFF

 

OFF

 

 

O

 

 

in the OFF Mode.

 

 

 

 

 

 

 

 

 

 

 

 

System Ready for

ON

X

OFF

OFF

OFF

 

OFF

 

O

 

 

 

Automatic Start

 

 

 

 

 

 

 

 

 

 

 

 

Generator Switch is

OFF

X

OFF

OFF

OFF

 

OFF

O

 

 

 

 

in the MANUAL Mode

 

 

 

 

 

 

 

 

 

 

 

 

Weekly Exerciser

X

Flashing

Flashing

Flashing

Flashing

 

Flashing

O

O

O

 

 

is not set

 

(-----------------------------------

1 sec rate

---------------------------------------

)

 

 

 

 

 

Battery Voltage <12V

X

ON

 

 

 

 

 

O

O

O

 

 

for >1 minute

 

(Non-latching)

 

 

 

 

 

 

 

 

 

 

Battery Voltage <6V

X

ON

 

 

 

 

 

O

O

 

 

 

Unit Shutdown due

OFF

X

ON

 

 

 

 

O

O

 

 

 

to Low Oil Pressure

 

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

X

 

ON

 

 

 

O

O

 

 

 

to High Temperature

 

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

X

 

 

ON

 

 

O

O

 

 

 

to Engine Overspeed

 

 

 

 

 

 

 

 

 

 

 

 

Unit Failed to Start

OFF

X

 

 

 

 

ON

O

O

 

 

 

during it’s Crank Cycle

 

 

 

 

 

 

 

 

 

 

 

 

Utility Voltage is

Flashing

X

 

 

 

 

 

O

O

 

 

 

<45% of Nominal

1 sec rate

 

 

 

 

 

 

 

 

 

 

 

Engine Speed Signal Fault

OFF

X

 

 

Flashing

 

 

O

O

 

 

 

Control Board is

OFF

X

The five RED LED’s will turn on one at a time

 

O

O

O

 

 

in GTS Mode

 

 

 

 

 

 

 

 

 

 

 

X = indicates that the LED can be ON or OFF depending on the operating conditions.

‹3.2.6 SYSTEM READY LED

The System Ready LED (green) has two main pro- poses. First, the LED will be ON when the AUTO/OFF/MANUAL switch is in the AUTO position, utility is present, and there are no system alarms. This ON state indicates the system is fully ready for automatic operation.

The system ready LED will be OFF when the switch is in the manual or OFF positions.

The system ready LED is also used to indicate the presence of utility sensing at the PCB when the switch is either in the AUTO or MANUAL modes. The LED will flash at the rate of 1/2 second on, 1/2 second off if the utility sensing level is below the transfer back threshold.

This secondary function is only available with dip switch two in the OFF position (ATS - automatic transfer switch application).

14 Generac® Power Systems, Inc.

3.3MANUAL TRANSFER AND

START-UP

To transfer electrical loads to the Standby (EMER- GENCY) power source side and start the engine man- ually, refer to the Owner’s Manual of the particular transfer switch.

3.4ENGINE GOVERNOR

ADJUSTMENTS

Engine speed governing is also controlled by the engine control board. The engine governor has been set by the factory during final testing of the generator and should not be adjusted.

If, however, adjustments are necessary, the following procedure should be followed (Figure 3.2 and Section 3.8):

1.Move dip switch 8 to the test mode (OFF posi- tion).

2.Set all three potentiometers (pots) fully counter- clockwise.

Page 16
Image 16
Generac Power Systems 005040-0, 005040-1, 005053-0, 005053-1, 005054-0, 005054-1 3.3MANUAL TRANSFER AND START-UP