Generac Power Systems 5251 Service Schedule, ATTENTION It is recommended that all service work

Models: 5253 5255 5251 5254 5252

1 72
Download 72 pages 53 Kb
Page 27
Image 27
4.12 SERVICE SCHEDULE

Section 4 — Maintenance

Air-cooled Generators

4.12 SERVICE SCHEDULE

ATTENTION: It is recommended that all service work

be performed by the nearest Authorized Dealer.

 

SYSTEM/COMPONENT

 

 

PROCEDURE

 

FREQUENCY

 

 

X = Action

Inspect

 

Change

 

Clean

W = Weekly

 

 

R = Replace as Necessary

 

 

 

 

 

M = Monthly

 

 

* = Notify Dealer

 

 

 

 

 

Y = Yearly

 

 

if Repair is Needed.

 

 

 

 

 

 

 

 

FUEL

 

 

 

 

 

 

 

 

Fuel lines and connections*

X

 

 

 

 

M

 

 

LUBRICATION

 

 

 

 

 

 

 

 

Oil level

X

 

 

 

 

M

 

 

Oil

 

 

X

 

 

EVERY 100 HOURS**

 

 

 

 

 

 

 

 

AND Y

 

 

Oil filter

 

 

X

 

 

EVERY 100 HOURS**

 

 

 

 

 

 

 

 

AND Y

 

 

COOLING

 

 

 

 

 

 

 

 

Enclosure louvers

X

 

 

 

X

W

 

 

BATTERY

 

 

 

 

 

 

 

 

Remove corrosion,

X

 

 

 

X

M

 

 

ensure dryness

 

 

 

 

 

 

 

 

Clean and tighten

X

 

 

 

X

M

 

 

battery terminals

 

 

 

 

 

 

 

 

Check charge state

X

 

R

 

 

EVERY 6 M

 

 

Electrolyte level

X

 

R

 

 

EVERY 6 M

 

 

(unsealed batteries only)*

 

 

 

 

 

 

 

 

ENGINE AND MOUNTING

 

 

 

 

 

 

 

 

Air cleaner

X

 

R

 

 

Y

 

 

Spark plug(s)

X

 

R

 

 

Y

 

 

GENERAL CONDITION

 

 

 

 

 

 

 

 

Vibration, Noise, Leakage,

X

 

 

 

 

M

 

 

Temperature*

 

 

 

 

 

 

 

 

COMPLETE TUNE-UP*

 

TO BE COMPLETED BY AN

 

Y

 

 

 

 

AUTHORIZED DEALER

 

 

 

 

 

 

 

 

 

 

 

 

*Contact the nearest Authorized Dealer for assistance if necessary.

**Change oil and filter after first eight (8) hours of operation and then every 100 hours thereafter. Change sooner when operating under a heavy load or in a dusty or dirty environment or in high ambient temperatures.

25

Page 27
Image 27
Generac Power Systems 5251, 5252, 5254 Service Schedule, ATTENTION It is recommended that all service work, Maintenance