Generac Power Systems 5415 Section TROUBLESHOOTING FLOWCHARTS, If Problem Involves AC Output

Models: 5410 5414 5415 5413 5411 5412

1 82
Download 82 pages 7.78 Kb
Page 27
Image 27
Section 6

Section 6

TROUBLESHOOTING FLOWCHARTS

Introduction

The “Flow Charts” in this section may be used in conjunction with the “Diagnostic Tests” of Section 7. Numbered tests in the Flow Charts correspond to identically numbered tests of Section 7.

Problems 1 through 4 apply to the AC generator only.

Beginning with Problem 5, the engine DC control sys- tem is dealt with.

If Problem Involves AC Output

TEST 1 – CHECK

NO-LOAD VOLTAGE

& FREQUENCY

VOLTAGE &

 

FREQUENCY GOOD –

 

FREQUENCY GOOD –

 

NO-LOAD VOLTAGE

FREQUENCY BOTH

 

VOLTAGE HIGH

 

ZERO OR RESIDUAL

 

& FREQUENCY

HIGH OR LOW

 

OR

 

VOLTAGE

 

GOOD

 

 

 

VOLTAGE LOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GO TO PROBLEM 1

 

GO TO VOLTAGE

 

GO TO PROBLEM 2

 

GO TO PROBLEM 4

 

 

 

REGULATOR ADUST-

 

 

 

 

 

 

 

 

 

MENT, PAGE xx

 

 

 

 

 

 

TEST 2 – CHECK STEPPER MOTOR CONTROL

Problem 1 – Voltage & Frequency Are Both High or Low

FREQUENCY GOOD.

 

 

GO TO

LOW OR RESIDUAL

 

 

 

 

PROBLEM 2

 

 

AC VOLTAGE

 

 

 

 

 

 

 

 

 

NO-LOAD FREQUENCY & VOLTAGE GOOD BUT THEY DROOP TO MUCH WHEN LOAD IS APPLIED

FREQUENCY IS GOOD BUT

NO-LOAD VOLTAGE IS

HIGH OR VOLTAGE IS LOW

GO TO

PROBLEM 4

GO TO VOLTAGE

REGULATOR

ADJUSTMENT,

PAGE 9

Page 25

Page 27
Image 27
Generac Power Systems 5415, 5412, 5411, 5413 Section TROUBLESHOOTING FLOWCHARTS, If Problem Involves AC Output, Introduction