TROUBLESHOOTING FLOWCHARTS

Problem 2 – Generator Produces Zero Voltage or Residual Voltage (5-12VAC)

TEST 11 – CHECK

MAIN CIRCUIT

BREAKER

RESET TO

“ON”

OR REPLACE

IF BAD

GOOD

 

TEST 4 – PERFORM

 

FIXED EXCITATION TEST

A

/ ROTOR AMP DRAW

 

 

 

 

B

C

D

TEST 8 – CHECK

BRUSH LEADS

GOOD

BAD

TEST 5 – CHECK

FIELD BOOST

BAD

TEST 6 – TEST STATOR DPE WINDING

GOOD

BAD

REPAIR

OR

REPLACE

TEST 9 –

CHECK

BRUSHES & SLIP RINGS

BAD

GOOD

REPAIR OR

REPLACE

THEN RE-TEST

INSULATION RESISTANCE TEST, PAGE 13

BAD

GOOD

REPAIR

OR

REPLACE

REPLACE VOLTAGE

REGULATOR

TEST 10 –

CHECK ROTOR

ASSEMBLY

BAD

TEST 7 – CHECK SENSING LEADS / POWER WINDINGS

GOOD

INSULATION RESISTANCE TEST, PAGE 13

BAD

REPAIR

OR

REPLACE

BAD

GOOD

TEST ROTOR

 

 

INSULATION,

 

BAD

 

PAGE 14

 

 

 

 

 

 

 