Section 7

DIAGNOSTIC TESTS

The greater the airflow through the carburetor venturi, the lower the pressure at the venturi throat. The lower the pressure at the venturi throat, the greater the dia- phragm movement, and the greater the movement of the regulator valve. The more the regulator valve opens, the greater the gas flow that is proportional to airflow through the generator.

The following facts about the secondary regulator must be emphasized:

The regulator must be sensitive to venturi throat pressure changes throughout the operating range.

The regulator must be properly adjusted so it will stop the flow of gas when the engine is not running (no air flow through the carburetor).

The slightest airflow (and vacuum in the venturi throat) should move the regulator valve off its seat and permit gas to flow.

Procedure:

A water manometer or a gauge that is calibrated in “ounces per square inch” may be used to measure the fuel pressure. Fuel pressure at the inlet side of the LPG Shut Off Valve should be between 11-14 inches water column as measured with a manometer. The LP system must be able to maintain 11-14 inches water column under all load requirements.

1.Turn LP supply to generator off.

2.Remove the Gas Pressure Tap from the fuel regu- lator and install manometer to this port.

3.Turn LP supply to generator on, the gauge should read 11-14 inches water column.

4.For Problem 8 only (Section 6), start the engine and the gauge should read 11-14 inches water column.

 

 

FUEL HOSE

GAS

 

BRASS

PRESSURE

 

HOSE

TAP

 

FITTING

Figure 7-29. – Fuel Regulator

RESULTS:

1.If the LP gas pressure is less than 11-14 inches water column the fuel supply system must be corrected in order to maintain 11-14 inches water column.

2.If the LP gas pressure is between 11-14 inches water Column, proceed to Test 26 for Problem 7 (Section 6). Proceed to Test 29 for Problem 8 (Section 6).

Test 26 – Check Wire 14 Power Supply

DISCUSSION:

When the engine is cranked, Printed Circuit Board action must deliver battery voltage to the Wire 14 cir- cuit, or the engine will not start. This is because the Wire 14 circuit will operate the Fuel Pump and Fuel Solenoid on Gasoline models. On LP models it oper- ates the LPG Shut-off valve.

PROCEDURE:

Inside the generator panel, locate the 4-tab Connector (Figure 7-30). Then, proceed as follows:

Figure 7-30. – The 4-tab Connector

1.Set a VOM to read battery voltage (12 VDC).

2.Connect the meter positive (+) test lead to the 4- tab Connector, the common (-) test lead to frame ground.

3.Crank the engine and the meter should read bat- tery voltage. If battery voltage is not measured, proceed to Step 4.

4.Check Wire 14 for poor connection from the 4-tab Connector to the Printed Circuit Board.

5.Crank the engine. The meter should indicate bat- tery voltage.

RESULTS:

1.If the meter indicated battery voltage, go to Test 20 “Check Start-Stop Switch”.

2.If battery voltage was NOT indicated in Step 3 but is indicated in Step 5, check Wire 14 between the 4-tab Connector and the Printed Circuit Board.

a.Repair, reconnect or replace Wire 14 as neces- sary.

3.If battery voltage was not indicated in Step 5, replace the Printed Circuit Board.

Page 52

Page 54
Image 54
Generac Power Systems 5412, 5411, 5413, 5415, 5414, 5410 manual Test 26 Check Wire 14 Power Supply, Fuel Regulator

5410, 5414, 5415, 5413, 5411 specifications

Generac Power Systems has established itself as a leading manufacturer of backup power solutions, particularly known for its range of generators designed for both residential and commercial use. Among their noteworthy products are the Generac models 5412, 5411, 5413, 5415, and 5414. Each of these generators showcases innovative technologies and features that enhance reliability, efficiency, and ease of use.

The Generac 5412 is a versatile model equipped with a robust 10 kW output, making it suitable for powering essential home appliances during outages. It operates using a 1.0 L engine that runs on natural gas or propane, providing flexibility in fuel options. The Quiet-Test feature is a notable characteristic, as it allows for a self-test at a reduced volume, minimizing noise disruptions during routine checks.

Moving to the Generac 5411, this generator offers a higher output capacity of 13 kW. It integrates advanced load management technology, which ensures that power is allocated efficiently among connected devices. This model also features a Mobile Link remote monitoring system, enabling users to check generator status and performance from anywhere via a smartphone app.

The Generac 5413 is tailored for larger residential needs, delivering an impressive 16 kW output. It boasts a durable all-weather aluminum enclosure designed for longevity against the elements. The 5413's integrated wifi connectivity allows for real-time monitoring and alerts, ensuring that homeowners are always informed of their generator's operating status.

For those seeking a balance of power and efficiency, the Generac 5415 offers 20 kW of output while maintaining a compact design. This model is enriched with the patented G-Flex technology, allowing it to adjust engine speed based on the load requirements, thereby conserving fuel and reducing noise levels. Additionally, the 5415 comes with an intuitive user interface for effortless operation and programming.

Finally, the Generac 5414 rounds out the lineup with its strong 24 kW capability. This model is particularly known for its Smart Management modules, which facilitate the safe and efficient distribution of power. Its intuitive design also includes a user-friendly control panel for straightforward operation, ensuring that homeowners, regardless of technical expertise, can utilize the system effectively.

In summary, Generac Power Systems’ 5412, 5411, 5413, 5415, and 5414 generators exemplify advanced power technology, tailored for reliability and user convenience. Whether for essential home functions or more extensive power needs, these models provide effective solutions to ensure that homes remain powered during outages.