Generac Power Systems R-200A technical manual Switch Position Condition System Low

Models: R-200A

1 16
Download 16 pages 25.92 Kb
Page 6
Image 6

General Information

R-panel Technical Manual

 

 

 

 

 

 

 

 

 

Switch Position

 

 

Condition

System

Low

Low

Low

High

Over

Over

Manual

Auto

Off

 

 

 

Ready

Fuel

Bat

Oil

Temp

Speed

Crank

 

 

 

 

 

Generator Switch is

OFF

@

X

OFF

OFF

OFF

OFF

 

 

O

 

 

in the OFF Mode

 

 

 

 

 

 

 

 

 

 

 

 

System Ready for

ON

@

X

OFF

OFF

OFF

OFF

 

O

 

 

 

Automatic Start

 

 

 

 

 

 

 

 

 

 

 

 

Generator Switch is

OFF

@

X

OFF

OFF

OFF

OFF

O

 

 

 

 

in the MANUAL Mode

 

 

 

 

 

 

 

 

 

 

 

 

Weekly Exerciser

X

@

Flashing

Flashing

Flashing

Flashing

Flashing

O

O

O

 

 

is not Set (Note A)

 

 

(---------------------------------------1 sec rate -------------------------------------)

 

 

 

 

 

Battery Voltage <12.2V

X

@

ON

 

 

 

 

O

O

O

 

 

for > 1 minute

 

 

(Non-Latching)

 

 

 

 

 

 

 

 

 

Battery Voltage <6V

OFF

@

ON

 

 

 

 

O

O

 

 

 

For > 0.05 seconds

 

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

@

X

ON

 

 

 

O

O

 

 

 

To Low Oil Pressure

 

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

@

X

 

ON

 

 

O

O

 

 

 

To High Cooant Temp

 

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

@

X

 

 

ON

 

O

O

 

 

 

To Engine Overspeed

 

 

 

 

 

 

 

 

 

 

 

 

Unit Failed to Start

OFF

@

X

 

 

 

ON

O

O

 

 

 

During it's Crank Cycle

 

 

 

 

 

 

 

 

 

 

 

 

Utility Voltage is

Flashing

@

X

 

 

 

 

O

O

 

 

 

< 60% of Nominal

1 sec rate

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

@

X

 

Flashing

 

 

O

O

 

 

 

To Low Coolant Level

 

 

 

 

 

 

 

 

 

 

 

 

Engine Speed Signal

OFF

@

X

 

 

Flashing

 

O

O

 

 

 

Fault/RPM Signal Loss

 

 

 

 

 

 

 

 

 

 

 

 

Control Board is

Flashing

@

X

 

 

 

 

O

O

O

 

 

In GTS Mode

5 sec ON, 1 sec OFF

 

 

 

 

 

 

 

 

 

 

 

DIP Switch #5 is

OFF

@

ON

ON

ON

ON

ON

O

O

O

 

 

not set correctly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

@= Low Fuel Pressure is a Yellow LED and will be ON when fuel pressure is less than 5 inches Water Column X = indicates that the LED can be ON or OFF depending on the Operating Mode (i.e. Manual, OFF or Auto) Note A: a RED LED fault indication has priority over the flashing LED's used to indicate exercise time not set