Goodman Mfg Multi-Position, Two-Stage/Variable-Speed Gas Furnace GCV9 COOLING SPEEDS, SS-GMV95

Models: GMV95/GCV9 Multi-Position, Two-Stage/Variable-Speed Gas Furnace

1 16
Download 16 pages 46.91 Kb
Page 9
Image 9
GCV9 COOLING SPEEDS

PRODUCT SPECIFICATIONS

GCV9 COOLING SPEEDS

HIGH- /SINGLE-STAGE & LOW-STAGE COOLING SPEEDS

 

GCV90704CXA

 

Cooling

Adjust

CFM at .1” to .8” w.c. ESP

Speed

 

High/Single-

Tap

Low Stage

Tap

Stage

 

 

 

Minus (-)

378*

540

A

Normal

390

600

 

Plus(+)

429

660

 

Minus (-)

468

720

B

Normal

520

800

 

Plus(+)

572

880

 

Minus (-)

644

990

C

Normal

715

1,100

 

Plus(+)

787

1,210

 

Minus (-)

836

1,286

D

Normal

929

1,429

 

Plus(+)

1,022

1,572

* Motor CFM maximum

 

GCV91155DXA

 

Cooling

Adjust

CFM at .1” to .8” w.c. ESP

Speed

 

High/Single-

Tap

Low Stage

Tap

Stage

 

 

 

Minus (-)

500*

705

A

Normal

508

783

 

Plus(+)

559

861

 

Minus (-)

621

982

B

Normal

690

1,091

 

Plus(+)

759

1,200

 

Minus (-)

815

1,265

C

Normal

906

1,406

 

Plus(+)

997

1,547

 

Minus (-)

1,049

1,628

D

Normal

1,165

1,809

 

Plus(+)

1,282

1,990

 

GCV90905DXA

 

Cooling

Adjust

CFM at .1” to .8” w.c. ESP

Speed

 

High/Single-

Tap

Low Stage

Tap

Stage

 

 

 

Minus (-)

513*

720

A

Normal

520

800

 

Plus(+)

572

880

 

Minus (-)

644

990

B

Normal

715

1,100

 

Plus(+)

787

1,210

 

Minus (-)

819

1,260

C

Normal

910

1,400

 

Plus(+)

1,001

1,540

 

Minus (-)

1,053

1,620

D

Normal

1,170

1,800

 

Plus(+)

1,287

1,980

* Motor CFM maximum

* Motor CFM maximum

Notes:

These charts are for furnaces installed at 0 - 2000 feet. At higher altitudes, a properly derated unit will have the same temperature rise at a particular CFM, while the ESP at that CFM will be lower.

The installation must be adjusted to obtain a temperature rise within the range listed on the furnace nameplate.

Do not operate above .5” w.c. ESP in heating mode.

Propane gas installations will have a High Stage rise approximately 4° lower than shown in above table.

SS-GMV95

www.goodmanmfg.com

9

 

 

 

Page 9
Image 9
Goodman Mfg Multi-Position, Two-Stage/Variable-Speed Gas Furnace GCV9 COOLING SPEEDS, Product Specifications, SS-GMV95