GCV9 HEATING SPEEDS

PRODUCT SPECIFICATIONS

GCV9 HEATING SPEEDS

GCV90704CXA (Rise Range: 30 - 60°F)

Heating

Adjust

Low-Stage

High-Stage

Rise

Speed Tap

Tap

CFM

CFM

 

 

 

 

 

 

 

Minus (-)

747

1,076

56

A

Normal

830

1,195

50

 

Plus(+)

913

1,315

46

 

Minus (-)

824

1,186

51

B

Normal

915

1,318

46

 

Plus(+)

1,007

1,449

42

 

Minus (-)

900

1,296

47

C

Normal

1,000

1,440

42

 

Plus(+)

1,100

1,584

38

 

Minus (-)

978

1,408

43

D

Normal

1,085

1,562

39

 

Plus(+)

1,194

1,719

35

GCV91155DXA (Rise Range: 30 - 60°F)

Heating

Adjust

Low-Stage

High-Stage

Rise

Speed Tap

Tap

CFM

CFM

 

 

 

 

 

 

 

Minus (-)

1,093

1,583

63

A

Normal

1,214

1,759

56

 

Plus(+)

1,335

1,935

51

 

Minus (-)

1,106

1,612

61

B

Normal

1,229

1,791

55

 

Plus(+)

1,352

1,970

50

 

Minus (-)

1,166

1,654

60

C

Normal

1,296

1,838

54

 

Plus(+)

1,426

2,022

49

 

Minus (-)

1,172

1,690

59

D

Normal

1,302

1,878

53

 

Plus(+)

1,432

2,066

48

GCV90905DXA (Rise Range: 30 - 60°F)

Heating

Adjust

Low-Stage

High-Stage

Rise

Speed Tap

Tap

CFM

CFM

 

 

 

 

 

 

 

Minus (-)

999

1,439

56

A

Normal

1,110

1,598

50

 

Plus(+)

1,221

1,758

46

 

Minus (-)

1,067

1,536

52

B

Normal

1,185

1,706

47

 

Plus(+)

1,303

1,876

43

 

Minus (-)

1,134

1,633

49

C

Normal

1,260

1,814

44

 

Plus(+)

1,386

1,996

40

 

Minus (-)

1,202

1,730

46

D

Normal

1,335

1,922

42

 

Plus(+)

1,469

2,115

38

Notes:

These charts are for furnaces installed at 0 - 2000 feet. At higher altitudes, a properly derated unit will have the same temperature rise at a particular CFM, while the ESP at that CFM will be lower.

The installation must be adjusted to obtain a temperature rise within the range listed on the furnace nameplate.

Do not operate above .5” w.c. ESP in heating mode.

Propane gas installations will have a High Stage rise approximately 4° lower than shown in above table.