
TROUBLESHOOTING CHART
SYMPTOM | POSSIBLE CAUSE | REMEDY | 
High head - low suction  | a. Restriction in liquid line or flowrator  | a. Remove or replace with proper size flowrator.  | 
High head - high or normal suction  | a. Dirty condenser coil  | a. Clean coil.  | 
  | b. Overcharged  | b. Correct System charge.  | 
  | c. Condenser fan not running  | c. Repair or Replace.  | 
Low head - high suction  | a. Incorrect flowrator  | a. Replace with correct flowrator.  | 
  | b. Defective compressor valves  | b. Replace compressor.  | 
  | c. Flowrator not seating properly  | c. Check for debris under flowrator or deformed  | 
  | 
  | flowrator. Remove debris or replace flowrator.  | 
  | d. Defective reversing valve  | d. Replace reversing valve.  | 
  | 
  | 
  | 
Unit will not run  | a. Power off or loose electrical connection  | a. Check for unit voltage at contactor in unit.  | 
  | b. Thermostat out of calibration set too high  | b. Reset.  | 
  | c. Defective contactor  | c. Check for 24 volts at contactor coil replace if  | 
  | 
  | contacts are open.  | 
  | d. Blown fuses or tripped breaker  | d. Replace fuse or reset breaker.  | 
  | e. Transformer defective  | e. Check wiring - replace transformer. | 
  | f. High or low pressure control open  | f. Reset high pressure control or check unit charge.  | 
  | (Optional)  | 
  | 
  | 
  | High pressure control opens at 610 psig.  | 
  | 
  | Low pressure control opens at 22 psig.  | 
  | g. Compressor overload contacts open  | g. Replace compressor.  | 
  | 
  | NOTE: Wait at least 2 hours for overload to reset.  | 
  | 
  | 
  | 
Condenser fan runs,  | a. Loose connection  | a. Check for unit voltage at compressor check &  | 
compressor doesn't  | 
  | tighten all connections.  | 
  | b. Compressor stuck, grounded or open  | b. Wait at least 2 hours for overload to reset If still  | 
  | winding open internal overload  | open, replace the compressor.  | 
  | c. Low voltage connection  | c. At compressor terminals, voltage must be within  | 
  | 
  | 10 % of nameplate volts when unit is operating.  | 
  | d. Capacitor weak, open, or shorted  | d. Check capacitor. If defective, replace.  | 
  | 
  | 
  | 
Low suction - cool compressor  | a. Low indoor airflow  | a. Increase speed of blower or reduce restriction -  | 
Iced evaporator coil  | 
  | replace air filters.  | 
Compressor short cycles  | a. Defective overload protector  | a. Replace - check for correct voltage.  | 
  | b. Unit cycling on low pressure control  | b. Check refrigerant charge and / or airflow.  | 
  | 
  | 
  | 
Registers sweat  | a. Low airflow  | a. Increase speed of blower or reduce restriction  | 
  | 
  | replace air filters.  | 
High suction pressure  | a. Excessive load  | a. Recheck load calculation.  | 
  | b. Defective compressor  | b. Replace.  | 
  | c. Reversing valve not seating properly.  | c. Replace.  | 
Insufficient cooling  | a. Improperly sized unit  | a. Recalculate load.  | 
  | b. Improper airflow  | b. Check - should be approximately 400 CFM per  | 
  | 
  | ton.  | 
  | c. Incorrect refrigerant charge.  | c. Charge per procedure attached to unit service  | 
  | 
  | panel.  | 
  | d. Incorrect voltage  | d. At compressor terminals, voltage must be within  | 
  | 
  | 10% of nameplate volts when unit is operating.  | 
  | 
  | 
  | 
14