Goodman Mfg IO - 395 Troubleshooting Chart, e. Check wiring - replace transformer, Symptom

Models: IO - 395

1 16
Download 16 pages 26.73 Kb
Page 14
Image 14
TROUBLESHOOTING CHART

TROUBLESHOOTING CHART

SYMPTOM

POSSIBLE CAUSE

REMEDY

High head - low suction

a. Restriction in liquid line or flowrator

a. Remove or replace with proper size flowrator.

High head - high or normal suction

a. Dirty condenser coil

a. Clean coil.

 

b. Overcharged

b. Correct System charge.

 

c. Condenser fan not running

c. Repair or Replace.

Low head - high suction

a. Incorrect flowrator

a. Replace with correct flowrator.

 

b. Defective compressor valves

b. Replace compressor.

 

c. Flowrator not seating properly

c. Check for debris under flowrator or deformed

 

 

flowrator. Remove debris or replace flowrator.

 

d. Defective reversing valve

d. Replace reversing valve.

 

 

 

Unit will not run

a. Power off or loose electrical connection

a. Check for unit voltage at contactor in unit.

 

b. Thermostat out of calibration set too high

b. Reset.

 

c. Defective contactor

c. Check for 24 volts at contactor coil replace if

 

 

contacts are open.

 

d. Blown fuses or tripped breaker

d. Replace fuse or reset breaker.

 

e. Transformer defective

e. Check wiring - replace transformer.

 

f. High or low pressure control open

f. Reset high pressure control or check unit charge.

 

(Optional)

 

 

 

High pressure control opens at 610 psig.

 

 

Low pressure control opens at 22 psig.

 

g. Compressor overload contacts open

g. Replace compressor.

 

 

NOTE: Wait at least 2 hours for overload to reset.

 

 

 

Condenser fan runs,

a. Loose connection

a. Check for unit voltage at compressor check &

compressor doesn't

 

tighten all connections.

 

b. Compressor stuck, grounded or open

b. Wait at least 2 hours for overload to reset If still

 

winding open internal overload

open, replace the compressor.

 

c. Low voltage connection

c. At compressor terminals, voltage must be within

 

 

10 % of nameplate volts when unit is operating.

 

d. Capacitor weak, open, or shorted

d. Check capacitor. If defective, replace.

 

 

 

Low suction - cool compressor

a. Low indoor airflow

a. Increase speed of blower or reduce restriction -

Iced evaporator coil

 

replace air filters.

Compressor short cycles

a. Defective overload protector

a. Replace - check for correct voltage.

 

b. Unit cycling on low pressure control

b. Check refrigerant charge and / or airflow.

 

 

 

Registers sweat

a. Low airflow

a. Increase speed of blower or reduce restriction

 

 

replace air filters.

High suction pressure

a. Excessive load

a. Recheck load calculation.

 

b. Defective compressor

b. Replace.

 

c. Reversing valve not seating properly.

c. Replace.

Insufficient cooling

a. Improperly sized unit

a. Recalculate load.

 

b. Improper airflow

b. Check - should be approximately 400 CFM per

 

 

ton.

 

c. Incorrect refrigerant charge.

c. Charge per procedure attached to unit service

 

 

panel.

 

d. Incorrect voltage

d. At compressor terminals, voltage must be within

 

 

10% of nameplate volts when unit is operating.

 

 

 

14

Page 14
Image 14
Goodman Mfg IO - 395 Troubleshooting Chart, e. Check wiring - replace transformer, Symptom, Possible Cause, Remedy