SERVICING
COOLING /HEAT PUMP- SERVICE ANALYSIS GUIDE
Complaint |
|
| No Cooling |
|
|
| Unsatisfactory Cooling/Heating |
| System Operating |
|
| ||||||||||
|
|
|
|
|
|
| Pressures |
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ProcedureServiceSee Ref. |
POSSIBLE CAUSE | notwillSystemstart | FanCond.andComp.will not start | willfanEvaporatornot start | willfanCondensernot start | oncyclesCompressoroverload | toothenandcoolToowarm | warmonenoughcoolNot days | otherscool,tooareasCertaintoo warm | noisyisCompressor | terminatenotwillUnitdefrost | defrostnotwillUnit | pressuresuctionLow | pressureheadLow | pressuresuctionHigh | pressureheadHigh | Test Method Remedy | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
DOTS IN ANALYSIS GUIDE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
INDICATE SYMPTOM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
"POSSIBLE CAUSE" |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pow er Failure | • |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Voltage | |
Blow n Fuse | • |
| • |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Inspect Fuse Size & Type | |
Unbalanced Pow er, 3PH |
| • |
|
|
| • | • |
|
|
|
|
|
|
|
|
|
|
|
| Test Voltage | |
Loose Connection | • |
|
| • |
| • |
|
|
|
|
|
|
|
|
|
|
|
|
| Inspect Connection - Tighten | |
Shorted or Broken Wires | • | • | • | • | • | • |
|
|
|
|
|
|
|
|
|
|
|
|
| Test Circuits With Ohmmeter | |
Open Fan Overload |
|
|
| • | • |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Continuity of Overload | |
Faulty Thermostat | • |
| • | • |
|
|
|
| • |
|
|
|
|
|
|
|
|
|
| Test continuity of Thermostat & Wiring | |
Faulty Transformer | • |
| • |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Check control circuit w ith voltmeter | |
Shorted or Open Capacitor |
| • |
|
| • | • | • |
|
|
|
|
|
|
|
|
|
|
|
| Test Capacitor | |
Internal Compressor Overload Open |
| • |
|
|
|
|
|
|
|
|
|
| ♦ |
|
|
|
|
|
| Test Continuity of Overload | |
Shorted or Grounded Compressor |
| • |
|
|
| • |
|
|
|
|
|
|
|
|
|
|
|
|
| Test Motor Windings | |
Compressor Stuck |
| • |
|
|
| • | • |
|
|
|
|
| ♦ |
|
|
|
|
|
| Use Test Cord | |
Faulty Compressor Contactor |
|
| • |
| • | • |
|
|
|
|
|
|
|
|
|
|
|
|
| Test continuity of Coil & Contacts | |
Compressor High Stage Not Working |
|
|
|
|
|
|
| • |
| • |
|
| ♦ |
|
|
|
|
|
| Test Voltage to Unloader Plug, Test Plug | |
Open Control Circuit |
|
|
| • |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Control Circuit w ith Voltmeter | |
Low Voltage |
| • |
|
|
| • | • |
|
|
|
|
|
|
|
|
|
|
|
| Test Voltage | |
Faulty Evap. Fan Motor |
|
|
| • |
|
|
|
|
|
|
|
|
|
|
| • |
|
| ♦ | Repair or Replace | |
Shorted or Grounded Fan Motor |
|
|
|
| • |
|
|
|
|
|
|
|
|
|
|
|
|
| • | Test Motor Windings | |
Improper Cooling Anticipator |
|
|
|
|
|
| • |
| • |
|
|
|
|
|
|
|
|
|
| Check resistance of Anticipator | |
Shortage of Refrigerant |
|
|
|
|
|
| • | • |
|
|
|
| ♦ |
|
| • | • |
|
| Test For Leaks, Add Refrigerant | |
Restricted Liquid Line |
|
|
|
|
|
| • | • |
|
|
|
|
|
|
| • | • |
| • | Remove Restriction, Replace Restricted Part | |
Open Element or Limit on Elec. Heater |
|
|
|
|
|
|
| ♦ |
|
|
|
| ♦ |
|
|
|
|
|
| Test Heater Element and Controls | |
Dirty Air Filter |
|
|
|
|
|
|
| • |
| • | • |
|
|
|
| • |
|
| ♦ | Inspect |
|
Dirty Indoor Coil |
|
|
|
|
|
|
| • |
| • | • |
|
|
|
| • |
|
| ♦ | Inspect Coil - Clean |
|
Not enough air across Indoor Coil |
|
|
|
|
|
|
| • |
| • | • |
|
|
|
| • |
|
| ♦ | Check Blow er Speed, Duct Static Press, Filter | |
Too much air across Indoor Coil |
|
|
|
|
|
|
|
|
| • |
|
|
|
|
|
| ♦ | • |
| Reduce Blow er Speed | |
Overcharge of Refrigerant |
|
|
|
|
| • | • |
|
|
|
| • | ♦ |
|
|
|
| • | • | Recover Part of Charge | |
Dirty Outdoor Coil |
|
|
|
|
| • | • |
|
| • |
|
|
|
|
| ♦ |
|
| • | Inspect Coil - Clean |
|
Noncondensibles |
|
|
|
|
|
| • |
|
| • |
|
| ♦ |
|
|
|
|
| • | Recover Charge, Evacuate, Recharge | |
Recirculation of Condensing Air |
|
|
|
|
|
| • |
|
| • |
|
|
|
|
|
|
|
| • | Remove Obstruction to Air Flow |
|
Infiltration of Outdoor Air |
|
|
|
|
|
|
| • |
| • | • |
|
|
|
|
|
|
|
| Check Window s, Doors, Vent Fans, Etc. |
|
Improperly Located Thermostat |
|
|
|
|
| • |
|
| • |
|
|
|
|
|
|
|
|
|
| Relocate Thermostat |
|
Air Flow Unbalanced |
|
|
|
|
|
|
|
| • |
| • |
|
|
|
|
|
|
|
| Readjust Air Volume Dampers |
|
System Undersized |
|
|
|
|
|
|
| • |
| • |
|
|
|
|
|
|
|
|
| Refigure Cooling Load |
|
Broken Internal Parts |
|
|
|
|
|
|
|
|
|
|
| • | ♦ |
|
|
|
|
|
| Replace Compressor | |
Broken Valves |
|
|
|
|
|
|
| • |
|
|
| • |
|
|
| • | • |
|
| Test Compressor Efficiency | |
Inefficient Compressor |
|
|
|
|
|
|
| • |
|
|
|
| ♦ |
|
|
| • | • |
| Test Compressor Efficiency | |
Loose |
|
|
|
|
|
|
|
|
|
|
| • |
|
|
|
|
|
|
| Tighten Bolts |
|
Faulty Reversing Valve |
|
|
|
|
| • |
|
|
|
|
|
| ♦ | ♦ | ♦ |
| ♦ | ♦ | ♦ | Replace Valve or Solenoid | |
Faulty Defrost Control |
|
|
|
| • |
|
|
|
|
|
|
| ♦ | ♦ | ♦ | ♦ | ♦ |
| ♦ | Test Control | |
Faulty Defrost Thermostat |
|
|
|
|
|
|
|
|
|
|
|
| ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | Test Defrost Thermostat | |
Flow rator Not Seating Properly |
|
|
|
|
|
|
| • |
|
|
|
|
|
|
|
| • | • |
| Check Flow rator & Seat or Replace Flow rator | |
|
|
|
| • Cooling or Heating Cycle (Heat Pump) |
|
|
| ♦ Heating Cycle Only (Heat Pump) |
|