Troubleshooting Chart for ECM Variable Speed Air Circulator Blower Motors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Symptom

 

Fault Description(s)

Possible Causes

Corrective Action

 

Cautions and Notes

 

 

- Motor rocks

 

- This is normal start-up for

----

----

 

----

 

 

 

slightly

 

 

 

 

 

 

variable speed motor.

 

 

 

 

when starting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Manual disconnect switch off or

- Check 230 Vac power at motor.

 

 

 

 

 

 

 

 

door switch open.

- Check low voltage (24 Vac R to C) at motor.

- Turn power OFF prior to repair.

 

 

 

 

 

 

- Blown fuse or circuit breaker.

- Check low voltage connections

 

 

 

 

 

 

 

 

Wait 5 minutes after

 

 

 

 

 

- No movement.

- 24 Vac wires miswired.

(G, Y, W, R, C) at motor.

 

 

 

 

 

 

 

disconnecting power before

 

 

 

 

 

- Unseated pins in wiring

- Check for unseated pins in connectors

 

 

 

 

 

 

 

 

opening motor.

 

 

 

 

 

 

harness connectors.

on motor harness.

 

 

 

- Motor won't

 

 

 

- Handle electronic motor/control with care.

 

 

 

 

- Bad motor/control module.

- Test with a temporary jumper between R - G.

 

 

 

 

 

 

 

 

start.

 

 

- Moisture present in motor or control module.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Loose motor mount.

- Check for loose motor mount.

 

- Turn power OFF prior to repair.

 

 

 

 

 

- Motor rocks,

 

Wait 5 minutes after

 

 

 

 

 

- Make sure blower wheel is tight on shaft.

 

 

 

 

 

 

- Blower wheel not tight on motor shaft.

 

disconnecting power before

 

 

 

 

 

but won't start.

- Perform motor/control replacement check,

 

 

 

 

 

- Bad motor/control module.

opening motor.

 

 

 

 

 

 

ECM motors only.

 

 

 

 

 

 

 

 

 

- Handle electronic motor/control with care.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Motor

 

 

 

 

 

 

 

 

 

oscillates up &

 

- It is normal for motor to

 

 

 

 

 

 

 

down while

 

oscillate with

----

----

 

----

 

 

 

being tested

 

no load on shaft.

 

 

 

 

 

 

 

off of blower.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Variation in 230 Vac to motor.

- Check line voltage for variation or "sag".

 

 

 

 

 

 

 

 

- Unseated pins in wiring harness

- Check low voltage connections

 

 

 

 

 

 

 

- Varies up and down

connectors.

(G, Y, W, R, C) at

 

 

 

 

 

 

 

- Erratic CFM command from

motor, unseated pins in motor

 

- Turn power OFF prior to repair.

 

 

 

 

 

or intermittent.

 

 

 

 

 

 

"BK" terminal.

harness connectors.

 

 

 

 

- Motor starts,

 

 

 

 

 

 

 

 

- Improper thermostat connection or setting.

- Check-out system controls - Thermostat.

 

 

 

 

 

but runs

 

 

- Moisture present in motor/control module.

- Perform Moisture Check.*

 

 

 

 

 

erratically.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Incorrect or dirty filter(s).

- Does removing panel or filter

 

 

 

 

 

 

 

- "Hunts" or "puffs" at

reduce "puffing"?

 

 

 

 

 

 

 

- Incorrect supply or return ductwork.

- Check/replace filter.

 

- Turn power OFF prior to repair.

 

 

 

 

 

high CFM (speed).

 

 

 

 

 

 

- Incorrect blower speed setting.

- Check/correct duct restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Adjust to correct blower speed setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Moisture Check

 

 

 

 

 

 

 

 

 

- Connectors are

oriented "down" (or as recommended by equipment manufacturer).

- Arrange harnesses with "drip loop" under motor.

 

 

 

 

- Is condensate drain plugged?

 

- Check for low airflow (too much latent capacity).

 

 

 

 

- Check for undercharged condition.

 

- Check and plug leaks in return ducts,

cabinet.

 

 

Note: You must use the correct replacement control/motor module since they are factory programmed for specific operating modes. Even though they look alike, different modules may have completely different functionality. The ECM variable speed motors are c

Important Note: Using the wrong motor/control module voids all product warranties and may produce unexpected results.

SERVICING

CHART CONTINUED ON NEXT PAGE

Page 28
Image 28
Goodman Mfg R-410A manual Chart on Next

R-410A specifications

Goodman Manufacturing, a well-respected name in the HVAC industry, has made significant advancements with their R-410A refrigerant technology. R-410A, a hydrofluorocarbon (HFC), has positioned itself as a superior alternative to the older R-22 refrigerant, which has been phased out due to its ozone-depleting properties. Goodman’s commitment to energy efficiency and environmental sustainability is well reflected in their use of R-410A in their air conditioning and heat pump systems.

One of the main features of Goodman’s R-410A systems is their exceptional energy efficiency. The R-410A refrigerant operates at a higher pressure than R-22, which allows for better heat transfer and improved cooling capacity. This results in reduced energy consumption and lower utility bills for consumers. Goodman’s air conditioning units designed for use with R-410A are often rated with high Seasonal Energy Efficiency Ratio (SEER) ratings, making them an eco-friendly choice for residential and commercial applications.

Another notable technology employed by Goodman is their commitment to reliable performance through advanced compressor designs. Goodman's scroll compressors are optimized for R-410A, ensuring quieter operation and reducing vibration levels. These compressors are known for their efficiency and longevity, making them a favorite among homeowners seeking dependable and durable climate control solutions.

Goodman's multi-stage cooling systems that utilize R-410A offer precise temperature control and enhanced comfort. By controlling the speed of the compressor, Goodman’s units can adjust output according to the heating or cooling demand, maximizing comfort while minimizing energy waste. This adaptability not only enhances indoor air quality but also contributes to a greener environment by using less energy.

Furthermore, Goodman incorporates high-tech diagnostic controls into their systems. These controls provide real-time performance data, allowing homeowners and technicians to monitor system status and troubleshoot issues more easily. By using R-410A combined with these innovative technologies, Goodman emphasizes reliability and user-friendly operation.

In conclusion, Goodman Manufacturing’s use of R-410A refrigerant reflects their dedication to efficiency, reliability, and environmental stewardship in HVAC solutions. The combination of advanced compressor technologies, high energy efficiency, and innovative controls solidifies Goodman’s reputation as a leader in the industry, offering homeowners and businesses the comfort and peace of mind they deserve.