Goodman Mfg R-410A S-4CHECKING TRANSFORMER AND CONTROL CIRCUIT, S-8CHECKING CONTACTOR CONTACTS

Models: R-410A

1 47
Download 47 pages 31.4 Kb
Page 24
Image 24
S-4 CHECKING TRANSFORMER AND CONTROL CIRCUIT

SERVICING

S-4 CHECKING TRANSFORMER AND CONTROL CIRCUIT

A step-down transformer (208/240 volt primary to 24 volt sec- ondary) is provided with each package unit. This allows ample capacity for use with resistance heaters.

S-8 CHECKING CONTACTOR CONTACTS WARNING

1.Remove control panel cover or etc. to gain access to trans- former.

With power ON:

S-8 CHECKING CONTACTOR CONTACTS

DISCONNECT POWER SUPPLY BEFORE SERVICING.

SINGLE PHASE

1.Disconnect the wire leads from the terminal (T) side of the contactor.

2.With power ON, energize the contactor.

LINE VOLTAGE NOW PRESENT.

T2 SINGLE PHASET1

LINE VOLTAGE NOW PRESENT.

VOLT/OHM

METER

CC

2.

Using a voltmeter, check voltage across secondary voltage

 

side of transformer (R to C).

3.

No voltage indicates faulty transformer, bad wiring, or bad

 

splices.

4.

Check transformer primary voltage at incoming line voltage

 

connections and/or splices.

5If line voltage is present at the primary voltage side of the transformer and 24 volts is not present on the secondary side, then the transformer is inoperative. Replace.

S-7 CHECKING CONTACTOR AND/OR RELAYS

The compressor contactor and other relay holding coils are wired into the low or line voltage circuits. When the control circuit is energized the coil pulls in the normally open contacts or opens the normally closed contacts. When the coil is de- energized, springs return the contacts to their normal position.

DISCONNECT POWER SUPPLY BEFORE SERVICING.

1.Remove the leads from the holding coil.

2.Using an ohmmeter, test across the coil terminals.

If the coil does not test continuous, replace the relay or con- tactor.

L2 L1

Ohmmeter for testing holding coil

S-7 CHECKING CONTACTOR AND/OR RELAYS Voltmeter for testing contacts

TESTING COMPRESSOR CONTACTOR

(Single Phase)

3.Using a voltmeter, test across terminals.

A.L1 to L2 - No voltage. Check breaker or fuses on main power supply. If voltage present, proceed to step B.

B.T1 to T2 - Meter should read the same as L1 to L2 in step A. If voltage readings are not the same as step A, replace contactor.

THREE PHASE

Using a voltmeter, test across terminals:

A.L1-L2, L1-L3, and L2-L3 - If voltage is present, pro- ceed to B. If voltage is not present, check breaker or fuses on main power supply..

B.T1-T2, T1-T3, and T2-T3 - If voltage readings are not the same as in "A", replace contactor.

24

Page 24
Image 24
Goodman Mfg R-410A S-4CHECKING TRANSFORMER AND CONTROL CIRCUIT, S-8CHECKING CONTACTOR CONTACTS, Servicing, Single Phase