Goodman Mfg SSZ140181A service manual Performance Data, Performance Test

Models: SSZ140181A

1 26
Download 26 pages 60.6 Kb
Page 25
Image 25

PERFORMANCE DATA

PERFORMANCE TEST

All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:

If conditions vary from this, results will change as follows:

1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.

2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and high side pressures and power.

A properly operating unit should be within plus or minus 2 degrees of the subcooling value shown in the Heat Pump Specifications.

A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.

A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.

A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.

A properly operating unit should be within plus or minus 3 Amps of the typical value shown.

NOTE: Pressures are measured at the liquid and suction service valve ports.

25

Page 25
Image 25
Goodman Mfg SSZ140181A service manual Performance Data, Performance Test