Goodman Mfg service manual Heat Pump Specifications, SSZ140181A* - SSZ140601A

Models: SSZ140181A

1 26
Download 26 pages 60.6 Kb
Page 5
Image 5
HEAT PUMP SPECIFICATIONS

HEAT PUMP SPECIFICATIONS

SSZ140181A* - SSZ140601A*

Cooling Capacity, BTUH

Compressor

R.L. Amps

L.R. Amps

Low Pressure Switch - Open / Close High Pressure Switch- Open / Close

Condenser Fan Motor

Horsepower

F.L. Amps

Liquid Line, Inches O.D.*

Suction Line, Inches O.D.*

Refrigerant Charge

Power Supply

Minimum Circuit Ampacity(1)

Maximum Overcurrent Device(2)

Electrical Conduit Size

Power Supply (Inches)

Approximate Shipping Weight

SSZ140181A

SSZ140241A

SSZ140301A

SSZ140361A

SSZ140421A

SSZ140481A

SSZ140601A

 

 

 

 

 

 

 

18,000

24,000

30,000

36,000

42,000

48,000

60,000

 

 

 

 

 

 

 

8.97

12.82

14.10

16.67

17.95

19.87

26.41

48.0

58.3

73.0

79.0

112.0

109.0

130.0

95 PSIG/50 PSIG

95 PSIG/50 PSIG

95 PSIG/50 PSIG

95 PSIG/50 PSIG

95 PSIG/50 PSIG

95 PSIG/50 PSIG

95 PSIG/50 PSIG

610 PSIG/420 PSIG

610 PSIG/420 PSIG

610 PSIG/420 PSIG

610 PSIG/420 PSIG

610 PSIG/420 PSIG

610 PSIG/420 PSIG

610 PSIG/420 PSIG

1/12

1/6

1/6

1/4

1/4

1/4

1/4

0.6

0.9

1.1

1.5

1.5

1.5

1.5

 

 

 

 

 

 

 

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

3/4"

3/4"

3/4"

7/8"

7/8"

7/8"

1 1/8"

150.0

170.0

195.0

220.0

220.0

280.0

285.0

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

11.80

16.93

18.73

22.33

24.00

26.40

34.60

20

20

30

30

40

40

60

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

199

207

219

242

242

266

280

*Up to 35' in equivalent line length

(1)Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.

(2)May use fuses or HACR-type circuit breakers of the same size as noted.

NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.

Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general and electrical information.

5

Page 5
Image 5
Goodman Mfg service manual Heat Pump Specifications, SSZ140181A* - SSZ140601A