SPLIT SYSTEM HEATING PERFORMANCE

EXPANDED PERFORMANCE DATA

MODEL: SSZ140421A* / CA*F4860*6A*+TXV / MBR2000**-1

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

51.5

48.8

45.9

42.9

41.0

39.7

36.9

34.0

34.3

31.6

29.1

27.5

26.5

23.8

21.1

18.4

15.7

12.8

Delta T

34.1

32.3

30.4

28.4

27.1

26.3

24.4

22.5

22.7

20.9

19.3

18.2

17.5

15.7

13.9

12.1

10.4

8.5

KW

3.40

3.33

3.27

3.21

3.17

3.14

3.08

3.02

3.07

3.00

2.94

2.90

2.87

2.81

2.74

2.68

2.61

2.54

AMPS

15.2

14.1

13.2

12.4

12.0

11.8

11.1

10.6

10.1

9.7

9.2

9.0

8.9

8.5

7.9

7.5

6.9

6.3

COP

4.44

4.28

4.11

3.92

3.79

3.70

3.50

3.30

3.26

3.08

2.90

2.78

2.70

2.48

2.25

2.01

1.76

1.48

EER

15.2

14.6

14.0

13.4

12.9

12.6

12.0

11.3

11.2

10.5

9.9

9.5

9.2

8.5

7.7

6.9

6.0

5.1

HI PR

370

354

341

326

318

312

300

288

276

263

253

247

242

233

224

215

207

200

LO PR

142

132

123

113

107

103

95

84

76

68

60

56

53

45

39

33

29

23

EXPANDED PERFORMANCE DATA

MODEL: SSZ140481A* / CA*F4860*6A*+TXV / MBR2000**-1

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

57.8

54.7

51.5

48.2

46.0

44.6

41.4

38.2

36.6

33.8

31.1

29.4

28.3

25.4

22.5

19.6

16.8

13.7

Delta T

34.5

32.7

30.8

28.8

27.5

26.6

24.7

22.8

21.9

20.2

18.6

17.6

16.9

15.2

13.4

11.7

10.0

8.2

KW

3.98

3.90

3.83

3.75

3.71

3.68

3.60

3.53

3.65

3.57

3.49

3.44

3.41

3.32

3.24

3.16

3.08

3.00

AMPS

19.4

17.6

16.1

14.8

14.1

13.7

12.7

11.7

11.0

10.3

9.5

9.2

9.0

8.3

7.4

6.6

5.7

4.6

COP

4.25

4.10

3.94

3.76

3.63

3.55

3.36

3.17

2.94

2.77

2.61

2.50

2.43

2.24

2.03

1.82

1.59

1.34

EER

14.5

14.0

13.5

12.8

12.4

12.1

11.5

10.8

10.0

9.5

8.9

8.5

8.3

7.6

6.9

6.2

5.4

4.6

HI PR

408

391

376

359

351

344

331

318

304

291

279

272

267

257

247

237

229

221

LO PR

136

126

118

109

103

99

91

81

73

65

57

53

51

43

37

32

28

22

EXPANDED PERFORMANCE DATA

MODEL: SSZ140601A* / CA*F4860*6A*+TXV / MBE2000**-1

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

 

30

25

20

17

15

10

5

0

-5

-10

MBh

71.6

67.8

63.8

59.7

57.0

55.2

51.3

47.3

 

47.9

44.2

40.7

38.4

37.0

33.2

29.4

25.7

21.9

17.9

Delta T

35.9

33.9

32.0

29.9

28.5

27.6

25.7

23.7

 

24.0

22.1

20.4

19.2

18.5

16.6

14.7

12.8

11.0

9.0

KW

4.83

4.74

4.64

4.54

4.48

4.44

4.35

4.25

 

4.42

4.32

4.21

4.15

4.11

4.00

3.90

3.80

3.69

3.59

AMPS

24.7

22.3

20.4

18.8

17.9

17.4

16.0

14.8

 

13.9

12.9

12.0

11.5

11.3

10.4

9.2

8.2

7.1

5.7

COP

4.34

4.19

4.03

3.85

3.72

3.64

3.45

3.26

 

3.17

2.99

2.83

2.71

2.63

2.43

2.21

1.98

1.74

1.46

EER

14.8

14.3

13.8

13.1

12.7

12.4

11.8

11.1

 

10.8

10.2

9.7

9.3

9.0

8.3

7.5

6.8

5.9

5.0

HI PR

404

387

372

356

347

341

327

314

 

301

288

276

269

265

255

245

235

226

218

LO PR

136

126

119

109

103

99

91

81

 

73

65

57

53

51

43

37

32

28

22

High pressure is measured at the suction service valve ( the larger valve). Low pressure is measured at the gauge port connection.

Calculations are based on nominal CFM and 70 °F indoor dry bulb.

AMPS = Outdoor unit amps (comp.+fan) KW = Total system power