Greenheck Fan PVE-35 Factory Set Points - continued, MODULATING CONTROL FOR FAN SPEED 0-10 VDC

Models: PVE-45 PVE-20 PVE-35 PVE-55

1 32
Download 32 pages 19.04 Kb
Page 13
Image 13
Factory Set Points - continued

Factory Set Points - continued

Resetting the V1000 drive to factory defaults To reset the V1000 drive back to Greenheck factory defaults go to parameter A1-01 and set it to “2”. Then go to A1-03 and change it to “1110” and press enter. The drive is now reset back to the settings programmed at Greenheck. This option is not available on the J1000.

MODULATING CONTROL FOR FAN SPEED

(0-10 VDC)

 

Parameter

Setting

 

V1000

J1000

 

 

 

 

 

 

A1-01

Access Level

2

2

 

 

 

 

b1-17

VFD Start-Up Setting

1

1

 

 

 

 

C1-01

Acceleration Time

30 sec.

30 sec.

 

 

 

 

C1-02

Deceleration Time

30 sec.

30 sec.

C6-02

Carrier Frequency

1

1

 

 

 

 

d2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

Motor

Motor

FLA

FLA

 

 

H3-04

Terminal A1 Bias

50%

50%

 

 

 

 

A1-01

Access Level

0

0

CO2 SENSOR CONTROL FOR FAN SPEED

(1/2 speed WHEN C02 drops below 700 PPM) (FULL SPEED WHEN C02 RISES ABOVE 800 PPM)

 

Parameter

Setting

 

 

 

 

V1000

J1000

 

 

 

 

 

 

A1-01

Access Level

2

2

b1-01

Reference Source (Frequency)

0

0

 

 

 

 

b1-17

VFD Start-Up Setting

1

1

C1-01

Acceleration Time

30 sec.

30 sec.

 

 

 

 

C1-02

Deceleration Time

30 sec.

30 sec.

C6-02

Carrier Frequency

1

1

 

 

 

 

d1-01

Frequency Reference 1

60 Hz

30 Hz

d1-02

Frequency Reference 2

30 Hz

60 Hz

 

 

 

 

d2-02

Ref Lower Limit

50%

50%

 

 

 

 

E2-01

Motor Rated FLA

Motor

Motor

FLA

FLA

 

 

H3-10

A2 Not Used

F

NA

A1-01

Access Level

0

0

 

 

 

 

multispeed control FOR FAN SPEED

(1/3 or 1/2 speed reduction)

 

Parameter

Setting

 

 

 

 

V1000

J1000

 

 

 

 

 

 

A1-01

Access Level

2

2

 

 

 

 

b1-01

Reference Source (Frequency)

0

0

 

 

 

 

b1-17

VFD Start-Up Setting

1

1

 

 

 

 

C1-01

Acceleration Time

30 sec.

30 sec.

 

 

 

 

C1-02

Deceleration Time

30 sec.

30 sec.

C6-02

Carrier Frequency

1

1

 

 

 

 

d1-01

Frequency Reference 1

60 Hz

60 Hz

d1-02

Frequency Reference 2

40 Hz

40 Hz

 

 

 

 

d1-03

Frequency Reference 3

30 Hz

30 Hz

d1-04

Frequency Reference 4

60 Hz

60 Hz

 

 

 

 

d2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

Motor

Motor

FLA

FLA

 

 

H1-04

Multfunction Input Sel 4

3

3

(Terminal S4)

 

 

 

 

 

 

 

H1-05

Multifunction Input Sel 5

4

4

(Terminal S5)

 

 

 

 

 

 

 

H1-06

Multifunction Input Sel 6

5

NA

(Terminal S6)

 

 

 

H3-10

A2 Not Used

F

NA

 

 

 

 

A1-01

Access Level

0

0

 

 

 

 

Model PVe Heat Recovery Unit 13