VII) COMBO HEATING
This section serves as a guide for the installation and use of “Combo” heating systems utilizing a domestic water heater which has been specifically approved for such use (see Figure 19). It is written for those knowledgeable in the required trades and professionals involved in the design and installation of Combo Heating Systems.
It is the responsibility of the installer/designer to follow all applicable codes to ensure the effectiveness and safety of the installation.
System Requirements
The following requirements must be met for the installation of Combo Heating Systems:
1.The piping and components connected to the water heater for the space heating applications shall be suit- able for use with potable water. The system should be installed with new,
2.A water heater which will be used to supply potable water must not be connected to any heating system or components previously used with a
3.Do not use this heater as a replacement for an existing boiler installation.
4.If the space heating water system requires water with temperatures in excess of 60°C (140°F), a mixing valve, or other means to temper the water and reduce scald hazard potential, must be installed in the potable hot water supply.
5.If the heater is installed with a
6.Proper sizing of the water heater for the given space and potable heating application is essential to ensure adequate heating capacity. The sizing and installation of such combination system must be performed by quali- fied personnel and be in accordance with public utility requirements and/or codes having jurisdiction.
The sizing of the water heater should be based on the design heat loss of the structure to be heated plus the potable water requirements.
IT IS IMPORTANT THAT THE WATER HEATER USED BE OVERSIZED TO ALLOW ADEQUATE HEATING AND POTABLE WATER HEATING CAPACITY.
CHECK VALVE | CIRC. PUMP |
HOT WATER | COLD TO | ||
TO HOUSE | WATER HEATER | ||
|
|
|
|
|
|
|
|
WATER
HEATER
AIR
HANDLER
MASSACHUSETTS
CODE DOES NOT
ALLOW THIS TYPE
OF INSTALLATION.
RADIATOR OR RADIANT FLOOR PIPING ARE
VIABLE ALTERNATIVES TO AIR HANDLER.
Figure 19 Example Of Combo Heating Piping Schematic
– 21 –