Air Requirements

Important: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to cor- rosive elements in the atmosphere is excluded from war- ranty coverage.

Installations in or for certain places including, but not limited to, those listed below will require outdoor air for combustion due to chemical exposure:

Beauty shops

Photo processing labs Buildings with indoor pools

Water heaters installed in laundry, hobby or craft rooms Water heaters installed near chemical storage areas

In such circumstances, outdoor combustion air may reduce, but will not eliminate, the presence of corrosive chemicals in the air. Combustion air must be free of acid-forming chemi- cals such as sulfur, fluorine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, refrig- erants and many other commercial and household prod- ucts. When burned, vapors from these products form highly corrosive acid compounds. These products should not be stored or used near the water heater or air inlet.

The area in which the heater is located is classified as either “an unconfined space” or “a confined space”.

An unconfined space is defined as a space having a vol- ume not less than 50 cubic feet per 1000 BTU/hour (4.8 cubic metres per kilowatt) of combined input rating of all appliances using the space. Adjacent open rooms may be included as part of the unconfined space, provided there are no closeable doors between these rooms. An example of this is an open basement.

A confined space is one smaller than described above. For buildings using tight construction (newer and renovated structures), the air supply shall be introduced from the out- doors, regardless of whether the space is confined or unconfined.

Confined Space Air Requirements for Canadian Installations

Refer to Figure 5 (a), or (b), and Table 1 for proper sizing and location of combustion air ducts and openings. CHECK

LOCAL CODES.

(a). Two permanent openings shall be provided connecting the confined space (e.g., closet, small room) with the unconfined space. Each opening shall have a free area of one square inch per 1,000 BTU/hour input (22 cm²/kW) of all appliances in the confined space. The top opening shall be located as close to the ceiling as prac- tical but never lower than the top of the heater. (see Figure 5 (a)). The bottom opening shall be located nei- ther more than 450mm (18 in.), nor less than 150mm (6 in.), above floor level.

(b). When using a single air supply, the duct shall terminate within 300mm (12 in.) above and within 600mm (24 in.) horizontally of the burner level of the appliance having the largest input. For example: GSW’s water heaters’ burners are 150mm (6 in.) from the floor, plus 300mm

(a)

PERMANENT

OPENINGS

CONFINED

SPACEUNCONFINED SPACE

EQUIPMENT LOCATED IN CONFINED SPACES;

ALL AIR FROM INSIDE THE BUILDING.

 

 

 

 

 

 

 

300mm

 

 

(b)

CONFINED

 

(12 in.)

 

SPACE

 

 

(MIN)

 

 

GRADE

COMBINATION

COMBUSTION/

VENTILATION

AIR DUCT

600mm (24 in.)

450mm (18 in.)

BASEMENT INSTALLATION, EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS

Figure 5 Combustion Air Supply Openings And Ducts (Can.)

Combined Input

 

 

Acceptable Round

Required

Duct Size Diameter

of All Appliances

in Confined

Free Area

A**

 

B***

 

Space*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BTU / h

(kW / hr)

cm2

in.2

mm

 

in.

mm

 

in.

25,000

8

45

7

76

 

3

100

 

4

50,000

15

45

7

76

 

3

100

 

4

75,000

23

70

11

100

 

4

125

 

5

100,000

30

90

14

100

 

4

125

 

5

125,000

37

120

18

125

 

5

150

 

6

150,000

45

140

22

125

 

5

150

 

6

*All appliances refers to, and includes, those appliances using the same air source (e.g. water heater, furnace, boiler, clothes dryer etc.).

**Maximum allowable length of ductwork listed in column A is 6.1 equivalent metres (20 ft.).

***Maximum allowable length of ductwork listed in column B is 15.2 equivalent metres (50 ft.)

Table 1 Air Supply Sizing (Can.)

(12 in.) equals 450mm (18 in.) as shown in Figure 5 (b). All exterior vent openings are to be at least 300mm (12 in.) above the ground and clear of snow levels.

– 9 –

Page 9
Image 9
GSW 72090 manual Confined Space Air Requirements for Canadian Installations, Local Codes

72090 specifications

The GSW 72090 is a remarkable addition to the world of modern heating solutions, designed to provide efficient and effective space heating. It epitomizes advanced technology, reliability, and user-centric design, making it an ideal choice for homes and commercial spaces alike.

One of the main features of the GSW 72090 is its impressive heating capacity. Engineered to deliver optimal warmth, it can efficiently heat larger areas, ensuring that spaces remain comfortable even during the coldest months. The unit’s high-grade alloy construction enhances durability and helps maintain consistent performance over time.

A vital technology integrated into the GSW 72090 is its modulating control system. This system intelligently adjusts the temperature output based on the current heating demand, optimizing energy usage and contributing to lower utility bills. This efficiency not only benefits the consumer but also has a positive impact on the environment by reducing greenhouse gas emissions.

The GSW 72090 also boasts a sleek and modern aesthetic, making it an attractive addition to any space. Its design allows for easy installation and maintenance, ensuring that users can focus on comfort without worrying about the complexities of upkeep. The unit operates quietly, providing a peaceful environment without the disruptive noises often associated with traditional heating systems.

Incorporating safety features is another key characteristic of the GSW 72090. It includes overheat protection, which automatically turns the unit off if it detects excessive temperatures, ensuring a safe environment for occupants. Additionally, the product is constructed with materials that are resistant to corrosion and wear, enhancing longevity.

As an environmentally conscious option, the GSW 72090 is designed to comply with stringent energy efficiency regulations. Its performance not only meets but often exceeds the required standards, making it a smart choice for those looking to reduce their carbon footprint.

Overall, the GSW 72090 stands out due to its combination of advanced technologies, user-friendly features, aesthetic appeal, and commitment to safety and efficiency. Its multi-faceted capabilities make it a prime option for anyone seeking reliable and effective heating solutions in their home or business.