Failure code

TROUBLE SHOOTING

FAILURE CODE

POSSIBLE REASONS

(DISPLAYED ON LCD)

 

 

 

 

 

 

 

Faulty temperature sensor Tai

1

Sensor disconnected, or broken, or at wrong

position, or short circuit

 

 

 

 

 

Faulty temperature sensor Tc1

2

Sensor disconnected, or broken, or at wrong

 

position, or short circuit

 

 

 

Faulty temperature sensor Tc2

3

Sensor disconnected, or broken, or at wrong

position, or short circuit

 

 

Faulty temperature sensor Tm

4

Sensor disconnected, or broken, or at wrong

 

position, or short circuit

 

 

 

Faulty EEPROM on indoor

5

Faulty indoor unit PCB

unit PCB

 

 

 

Abnormal communication

 

Wrong connection, or the wires be disconnected,

6

or wrong address setting of indoor units, or faulty

between indoor and outdoor unit

 

PCB, or faulty power supply

 

 

 

 

 

 

Indoor unit address repeated

9

Wrong setting of indoor unit address

 

 

 

 

Central control address repeated

10

Wrong setting of centralized control indoor unit

address

 

 

 

 

 

 

Faulty indoor unit fan motor

11

Fan is blocked, or the terminal is disconnected

from the PCB, or faulty indoor unit PCB

 

 

 

 

 

 

Faulty driver of indoor unit

12

Faulty indoor unit PCB

fan motor

 

 

 

 

 

 

 

Malfunction on outdoor unit

20

Check the outdoor unit

 

 

 

 

Note:

1.Please contact the installers or distributors when trouble happens to repair it.

2.Turn the power off and power on again, if the failure code recurs, please change the indoor unit PCB.

3.Failrue codes maked with are resumable.