Oakleaf Woodburning Stove
B. Clearances To Combustibles
CLEARANCE TO COMBUSTIBLES: Vertical Venting Configuration
Location
AUnit to Side Wall
B Unit to Back Wall
C Vent Pipe to Side Wall
D* | Vent Pipe to Back Wall |
17" / 432 mm 14" / 356 mm 26.75" / 679 mm *17.5" / 444 mm
Pipe clearance may be reduced using double wall or insulated connector pipe, provided that you adhere to the specified clearances from the stove itself. Follow pipe manufacturer's guidelines.
C |
A |
D*
B
*NFPA 211 specifies 18" clearance to single wall connector pipe. This lower clearance is based on actual safety test conditions.
For clearance reduction methods, refer to NFPA 211 or Local Codes
CLEARANCE TO COMBUSTIBLES: Vertical Vent, Horizontal Exit
| Location |
|
A | Unit to Side Wall | 16" / 407 mm |
B | Unit to Back Wall | 13" / 330 mm |
C | Vent Pipe to Side Wall | 25.25" / 641 mm |
D* | Vent Pipe to Back Wall | *17" / 432 mm |
E* | Vent Pipe to Ceiling | *16" / 407 mm |
F | Minimum Vertical | 0" / 0 mm |
Pipe clearance may be reduced using double wall or insulated connector pipe, provided that you adhere to the specified clearances from the stove itself. Follow pipe manufacturer's guidelines.
*NFPA 211 specifies 18" clearance to single wall connector pipe. This lower clearance is based on actual safety test conditions.
| E |
F | C |
| A |
C |
A |
E |
D |
B |
10 Dry Seasoned Wood Only! | Save These Instructions |