Venting
NOTICE
Use only components specified by the venting manufacturer or the appliance manufacturer, including
the proper wall
components may cause exhaust spillage and/or increase fire risk.
#1 Preferred method
This method provides excellent venting for normal operation and allows the stove to be installed closest to the wall. Two inches from the wall is safe; however, four inches allows better access to remove the rear panel. The vertical portion of the vent should be three to five feet high. This vertical section will help provide natural draft in the event of a power failure. Note: Do not place joints within wall
3 ft.
to
Combustibles
Shaded area represents the minimum clearance to combustible materials such as shrubbery, mulch or tall grasses.
12" min. wall to outlet
Fig. 9
3 ft.
to Combustibles
Fig. 11
3 ft.
to
Combustibles
Fig. 10 |
| 3 ft. |
|
| to Combustibles |
#2 Preferred method
This method also provides excellent venting for normal operation but requires the stove to be installed farther from the wall. The vertical portion of the vent should be three to five feet high and at least three inches from a combustible wall. This vertical section will provide natural draft in the event of a power failure.
If the stove is installed below grade be sure the vent termination is at least 18" above grade. The outlet must also be 1 foot from the house/building.
Note: Do not place joints within wall pass- throughs.
CAUTION
Keep any materials that may be affected by the elevated exhaust temperatures at least 3 feet away from the flue termination
XXV Pellet Stove 11