Harman Stove Company R16 manual ESP Control, Status light error messages

Models: R16

1 44
Download 44 pages 50.75 Kb
Page 16
Image 16
ESP Control

ESP Control

Mode Selector

Allows you to choose between Room Temp Mode, Stove Temp Mode, or OFF. Also allows you to vary the distribution blower speed by turning the knob to the high or low side of each mode.

Distribution Blower speed adjustment range.

L = low H = high

Variable speed anywhere between L and H; although as the stove temp. goes up, so does the L and H scale.

Igniter switch

Set to appropriate Start-

Up mode.

Test

Runs all motors at full speed for one minute to check operation.

After a minute, the control will simulate a minimum burn and the combustion blower will remain on low.

Feed adjuster

Sets the maximum feed rate

Dealer Diagnostic Port

Temp dial

For dealer maintenance

Allows you to adjust the

only. Requires special DDM

room temperature in Room

monitor supplied to Harman

Temp Mode using the outer

Dealers exclusively.

scale marked in degrees

 

Fahrenheit. It also allows

 

you to adjust the stove

 

temperature while in Stove

 

Temp Mode using the inner

 

scale marked from 1 to 7.

 

Indicates igniter is on.

 

Indicates power to the feed

 

motor.

 

Indicates power to

 

combustion blower

 

Indicates power to

 

distribution blower.

 

Status Light

 

Will be lit in either stove

 

or room temp mode when

 

pointer is not within off

 

position band except after

 

normal shut down. Blinks to

 

indicate errors listed below.

 

Power Light

 

Indicates power to the

 

control.

Status light error messages:

3 Blinks: Indicates that the ESP (Exhaust Sensing Probe) has gone out of range too many times. If the unit seems to be operating correctly, perform a manual reset*.

4 Blinks: Can occur only in Room Temp Mode and indicates Room Sensing Probe failed or not installed. If a Room Sensing Probe is then installed, the status light will automatically reset.

NOTE: Unit will not start in "AUTO" with this status error.

5 Blinks (In Igniter Auto. Mode Only): Indicates that

the unit has failed to light within the 36 minute start cycle. To reset - Turn Mode Selector to "OFF", then turn to either mode again.)

6 Blinks : Indicates that the control has calculated poor or incomplete combustion occurring for more than 50 minutes.

A six blink status may be set if the stove is allowed to run out of pellets. To reset, turn mode selector to "OFF" then back on to the desired mode. If the unit was not out of pellets, see Troubleshooting section, Page 29, for more details.

*Manual reset- disconnect power cord for a few seconds and reconnect. If error still occurs call your Dealer.

16XXV Pellet Stove

Page 16
Image 16
Harman Stove Company R16 manual ESP Control, Status light error messages