Venting
Minimum flue vent configuration
It is recommended that outside air be installed with this venting configuration to reduce smoke and creosote smell in the room in the event of power failure.
Fig. 18
18"
Min. above ground level
12" min. wall to outlet
| 36" min clearance |
| to any materials that |
| may be affected by |
Fig. 19 | the elevated exhaust |
temperatures |
Vent Configurations:
To reduce probability of reverse drafting during
•Installing the pellet vent with a minimum vertical run of five feet, preferably terminating above the roof line.
•Installing the outside air intake at least four feet below the vent termination.
To prevent soot damage to exterior walls of the house and to prevent
•Maintain specified clearances to windows, doors, and air inlets, including air conditioners.
•Vents should not be placed below ventilated soffits. Run the vent above the roof.
•Avoid venting into alcove locations.
•Vents should not terminate under overhangs, decks or onto covered porches.
•Maintain minimum clearance of 12 inches from the vent termination to the exterior wall. If you see deposits developing on the wall, you may need to extend this distance to accommodate your installation conditions.
Hearth & Home Technologies assumes no responsibility for, nor does the warranty extend to, smoke damage caused by reverse drafting of pellet appliances under
XXV Pellet Stove 15