Special Instructions
Coil Installation:
Hot Water Out | Pressure |
| Cold Water In |
|
|
| |
| Relief Valve |
| Automatic |
| 1 |
| Air Valve |
|
| 2 | |
|
|
| |
|
|
| 5 |
|
|
| Pressure |
|
|
| Relief Valve |
|
|
| (Must be within |
|
|
| 2 feet of coil) |
| Existing Water | 3 | 3 |
|
| ||
|
|
| |
| Heater |
|
|
|
|
| 10 Feet Maximum |
Drain
Valve 4
Rear Of Furnace
Plumbing Diagram For
Place one of the supplied nuts on each leg of the coil. Place the coil through the holes on the back of the furnace, and adjust the nuts so that the pipes stick out about 1¼ to 1½ inches from the rear of the furnace. Place the flat washers and gaskets over each pipe and tighten the nuts. You are now ready to run the piping.
This simple method is the most economical. However, the existing water heater must be less than 10 feet from the furnace. The water inlet, where the Temperature / Pressure Relief valve is located, must be higher than the top leg of the water coil. The water heater should be elevated, if necessary, to allow for proper
A. Shut off the water heater and the water supply to it. Drain the tank completely.
B. Remove the Temp. / Presure relief valve and discard. Install a short 3/4 in. nipple and tee (1) along with a new relief valve.
C. run 3/4 in. copper tubing between the water tank and the top leg of the coil. Install a 3/4 in vent elbow and automatic “float type” air vent (2) in the high point of the line. Within 2 feet of the top leg of the coil, install a 150 lb. pressure relief valve (5). Run 3/4 in. tubing from the release exit of both relief valves downward (3) so the hot water can escape in the event of an overheat situation.
D. Remove the drain valve, at the bottom of the tank. Install a short 3/4 in. nipple and tee and
16