TL2.0 Woodburning Stove

C. Floor Protection Requirements

 

 

L

USA

 

 

J

 

J

 

K

CANADA

 

 

Floor Protection Requirements

If the appliance is being installed on a combustible floor, non-combustible floor protection must be installed. In all installations, the area under and around the stove must be protected from falling ash and live coals. The area under a horizontal run of chimney connector must also be protected, extending two (2) inches (51mm) to each side of the horizontal connector.

Further guidelines for floor protection are as follows: In the U.S. the floor protector must be completely under the stove, and extending 18" in front of the door opening, 8" to each side of the door opening, and 8" to the back.

In Canada, the floor protection must extend 18" (457mm) in front of the door opening, and 8" (203mm) to each side of the appliance, and to the rear.

Minimum Size floor protection (USA) is 48" Deep By 32.5" Wide.

Floor Protection

Inches

Millimeters

Requirements

 

 

J

Sides- USA /CANADA *

8

203

 

 

 

 

K

Front- USA /CANADA *

18

457

L

Rear- USA

8

203

L

Rear- CANADA

8

203

*Floor protection dimensions for the front and sides are measured from the appliance door opening in The United States. In Canada, the side dimension is measured from the widest part of the appliance.

The recommended floor protection for a corner installation is 60" (USA & CANADA).

60" / 1524 mm