TL2.0 Woodburning Stove
Chimney Breach Fireplace Conversion with Combustible Wall
Minimum Clearance from Chimney Connector to Un- protected Ceiling
| 16"** |
|
Flue Liner with Required Air Space |
|
|
Listed or Approved Thimble Assembly |
|
|
1" Clearance for Complex- | Combustible |
|
ity Exterior Chimney | Wall |
|
or |
|
|
2" Clearance for Interior | Sheetrock | Airtight |
Chimney and 2" Clear- |
| |
| insulated | |
ance for NFPA |
| |
| ||
Approved Thimbles |
|
|
| Mantel & Trim |
|
| Protection |
|
| Damper Closed and |
|
| Sealed with Non- |
|
| Combustible |
|
| Material. |
|
Floor Protection* |
|
|
Combustible Floor
*Floor Protection in Accordance with Solid Fuel Appliance Listing
**Check with your local building codes for clearance.
The Chimney Connector Shall Not Pass Through an Attic or Roof Space, Closet or Similar
Concealed Space, a Floor or Ceiling.
Save These Instructions | Dry Seasoned Wood Only! | 19 |