Harman Stove Company TL2.0 manual Minimum Clearance to Unprotected Ceil- ing

Models: TL2.0

1 40
Download 40 pages 37.87 Kb
Page 18
Image 18
Minimum Clearance to Unprotected Ceil- ing 16"

TL2.0 Woodburning Stove

Chimney Breach Fireplace Conversion with Non-Combustible Wall

Minimum Clearance to Unprotected Ceil- ing 16"

Chimney Connector

Sealed at Thimble

Flue Liner with Re- quired Air Space

Three Sheet Metal

Screws per Joint of

Chimney Connector

Mantel and Trim Pro- tection

Floor Protection*

Combustible Floor

*Floor Protection in Accordance with Solid Fuel Appliance Listing

Airtight

insulated Clean-out

Chimney ConnectorFlue Liner with Re- quired Air SpaceThree Sheet Metal Damper Closed and Sealed with Non-Combus- tible Material.

The Chimney Connector Shall Not Pass Through an Attic or Roof Space, Closet or Similar Concealed Space, a Floor or Ceiling.

18 Dry Seasoned Wood Only!

3-90-08560

Save These Instructions

Page 18
Image 18