SPECIFICATIONS
ELECTRICAL RATING CHART – FR2 MODELS
|
| Kilowatts |
|
| Wire Sizing | Fuse or |
|
Model | Voltage | (kW) | Phase | Amps | AWG*† | Circuit Breaker* | Shipping Weight |
208 | 3 | 1 | 14.5 | 12 | 20 | 24 lbs. (11 kg) | |
208 | 4 | 1 | 19.2 | 12 | 30 | 24 lbs. (11 kg) | |
208 | 6 | 1 | 28.8 | 10 | 40 | 27 lbs. (12 kg) | |
|
|
|
|
|
|
|
|
240 | 3 | 1 | 12.5 | 12 | 20 | 24 lbs. (11 kg) | |
240 | 4 | 1 | 16.7 | 12 | 30 | 24 lbs. (11 kg) | |
240 | 6 | 1 | 25.0 | 10 | 40 | 27 lbs. (12 kg) | |
208 | 3 | 3 | 8.4 | 14 | 15 | 24 lbs. (11 kg) | |
208 | 4 | 3 | 11.2 | 14 | 15 | 24 lbs. (11 kg) | |
208 | 6 | 3 | 16.7 | 12 | 30 | 27 lbs. (12 kg) | |
|
|
|
|
|
|
|
|
240 | 3 | 3 | 7.3 | 14 | 15 | 24 lbs. (11 kg) | |
240 | 4 | 3 | 9.6 | 14 | 15 | 24 lbs. (11 kg) | |
240 | 6 | 3 | 14.5 | 12 | 20 | 27 lbs. (12 kg) | |
|
|
|
|
|
|
|
|
208 | 8 | 1 | 38.4 | 8 | 50 | 27 lbs. (12 kg) | |
240 | 8 | 1 | 33.3 | 8 | 50 | 27 lbs. (12 kg) | |
|
|
|
|
|
|
|
|
208 | 9 | 3 | 25.0 | 10 | 40 | 27 lbs. (12 kg) | |
240 | 9 | 3 | 21.7 | 10 | 30 | 27 lbs. (12 kg) | |
|
|
|
|
|
|
|
|
208 | 12 | 3 | 33.4 | 8 | 50 | 27 lbs. (12 kg) | |
240 | 12 | 3 | 29.0 | 10 | 40 | 27 lbs. (12 kg) | |
|
|
|
|
|
|
|
|
* Based upon NEC 2002 Code
† Based upon THHN wire rated 90ºC.
NOTE: NSF Standard 4 has recently added performance requirements for food rethermalizing. The requirements mirror the requirements for food rethermalizing in the FDA Food Code. The basic requirement is that food reach a temperature of 165°F (74°C) in a time period of two hours or less.
Appliances that are manufactured for the purpose of rethermalizing food will need to meet these performance requirements in order to be listed to NSF Standard 4.
The Hatco FR2 Series heating unit is specifically made for food rethermalizing, however, the heating unit is designed to be incorporated into a hot water bath rethermalizer. Hatco does not supply the vessel that contains the water,
nor the system which determines how food is placed and held in the vessel. The Hatco FR2 unit attaches to the bottom of the vessel and supplies hot water to the vessel.
Hatco does supply sizing recommendations to enable the appliance manufacturer to correctly size the FR2 unit to the vessel. However, there are variables in the way that the vessel is manufactured that affect its ability to pass the NSF performance requirements. The Hatco FR2 unit is listed with NSF for construction only. Due to the fact that
the FR2 is only a portion of a larger system, it is impossible to do performance testing until the FR2 unit is incorporated onto the water vessel.
The result is that it is the responsibility of the vessel manufacturer to have the entire rethermalizing appliance tested and listed in accordance with NSF Standard 4. Simply hanging an NSF listed FR2 unit on the appliance does
not transfer NSF listing to the entire appliance.