E. Vent Diagrams

Top Vent - Horizontal Termination

Note: The 6000 series fireplaces can adapt to SLP series vent pipe, if desired.

When venting off the top of the unit, use a DVP-2SL adapter and a minimum 48 inch vertical section of SLP series vent pipe.

A DVP-SLP24 adapter may also be used with a 24 inch vertical section of SLP series vent pipe.

After the 48 inch vertical section, the venting table rules must be followed. The first 48 inch vertical section is NOT counted as part of the vertical components in the table. It is still counted as part of the overall maximum run. All venting table rules for the vent run must still be followed.

Example: DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal SLP pipe 7 ft. min. vertical = 11 ft. max. horizontal

Top Vent - Horizontal Termination

WARNING

Fire Risk. Explosion Risk.

Do NOT pack insulation or other combustibles between ceiling firestops.

ALWAYS maintain specified clearances around venting and firestop systems.

Install wall shield and ceiling firestops as speci- fied.

Failure to keep insulation or other material away from vent pipe may cause fire.

WARNING

Fire Risk.

When using DVP-HRC-SS and DVP-HRC-ZC- SS termination caps on top vented fireplaces, a 6 inch minimum vertical vent section is required before installing first elbow.

One Elbow

 

V1 Minimum

H1 Maximum

 

Elbow only

2 ft

610 mm

 

1 ft.

305 mm

3 ft.

914 mm

 

2 ft.

610 mm

6 ft.

1.8 m

 

3 ft.

914 mm

11 ft.

3.4 m

V1

4 ft.

1.2 m

20 ft.

6.1 m

H1

V1

+ H1 = 40 ft. (12.2 m) Maximum

 

H1 = 20 ft. (6.1 m) Maximum

Note: For corner installations: A 6 inch (152 mm) section of straight pipe may need to be attached to the appliance before a 90º elbow, to allow the vent pipe to clear the top standoffs.

Figure 7.3

Two Elbows

H2

Note: For corner installations: A 6 inch (152 mm) section of straight pipe may need to be attached to the appliance before a 90º elbow, to allow the vent pipe to clear the top standoffs.

V1

H1

V1 Minimum

H1 + H2 Maximum

Elbow only

1 ft.

305 mm

6 in.

152 mm

2 ft.

610 mm

1 ft.

305 mm

2 ft.

610 mm

2 ft.

610 mm

4 ft.

1.2 m

3 ft.

914 mm

9 ft.

2.7 m

4 ft.

1.2 m

18 ft.

5.5 m

5 ft.

1.5 m

20 ft.

6.1 m

V1 + H1 + H2 = 40 ft. (12.2 m) Maximum

H1 + H2 = 20 ft. (6.1 m) Maximum

 

INSTALLED

Figure 7.4

HORIZONTALLY

 

24

Heat & Glo • 6000GLX-IPI-S/-R, 6000GLX-IPILP-S/-R2101-900 Rev. S • 12/08

Page 24
Image 24