WARNING! Risk of Fire! Comply with all minimum clearances to combustibles as specified. Framing or finish- ing material closer than the minimums listed must be con- structed entirely of non-com- bustible materials (i.e., steel studs, concrete board, etc).

Ceiling or Overhang

12 in. (305 mm) max. combustible mantel depth

Structure Additionalor Sidewall

Fireplace

Structure

Mantel

Noncombustible

mat’l

 

 

82in.

(2083 mm)

minimum

height

49-1/2 in.

(1257 mm) minimum

25 in.

(635 mm) minimum

6 in.

(151 mm)

minimum - one side only. Alcove installations require 14 in. (356 mm) from each side of the firebox opening.

16 in. (406 mm)

deep non-combustible hearth extension recommended when floor in front is combustible.

Figure 3.3 Clearances

Outdoor Lifestyles by Hearth & Home Technologies Inc. • Carolina • 4066-300 • Rev. Q • 7/11