Cumberland Gap Wood Stove

FLOOR PROTECTION

Minimum Hearth Requirements ONLY

See page 6 for stove clearances

The floor must be non-combustible material, extending beneath heater and to the front/sides/rear as indicated. The floor must be a minimum of 1/2" thickness ("k" value = 0.84) non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks and falling embers. A layer of thin brick or ceramic tile over a combustible floor is not sufficient. See Alternate Floor Protection on page 8.

In USA installations, it is necessary to install a non-combustible floor protector at least 16" in front and 8" to both sides of the fuel loading doors. See *exception below.

In Canada, similar floor protection must be provided 18" (450mm) in front and 8" (200mm) from the sides and rear of the stove. See *exception below.

*EXCEPTION: Non-combustible floor protections must extend beneath the flue pipe when installed with horizontal venting and extend 2" (51mm) beyond each side.

NOTE: Drawings are for illustration purposes only and are not to scale.

SIDE FUEL DOOR LOCKED SHUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200mm (8")

12”

 

 

 

 

 

(305mm)

 

 

 

 

 

 

 

Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Front Fuel

loading door

16" (406mm) from fuel loading door

8" (200mm)

USA

200mm

 

200mm

1371mm

 

 

 

 

 

 

 

(54")

 

 

 

(8")

(8")

 

 

Minimum

 

 

 

 

 

 

 

39-1/8"

(994mm) Minimum

450mm (18")

CANADA

1089mm (42-7/8") Minimum

34-5/8"(879mm) Minimum

BOTH FUEL DOORS ACCESSIBLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8"(200mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuel loading doors

 

 

Minimum 16"

 

 

 

 

 

 

 

 

 

 

 

 

 

(406mm) from

39-

 

1/8"

Front

Side

 

 

 

 

 

 

 

fuel loading

(994mm)

 

 

 

 

 

 

door

Minimum

 

 

200mm

 

(8")

Mininum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

450mm

 

 

 

 

 

 

 

 

(18") from

 

200mm

 

 

 

 

 

fuel loading

 

Fuel loading doors

door.

 

 

 

 

(8")

 

 

1371mm

 

 

Front

Side

 

 

 

 

 

 

 

 

 

(54")

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

8"

(200mm)

Minimum 16" (406mm) from fuel loading door

USA

Mininum 450mm

 

(18") from fuel

 

loading door.

CANADA

 

44-7/8"(1140mm) Minimum

1295mm (51") Minimum

September 1, 2008

7006-188E

Page 7

Page 7
Image 7
Hearth and Home Technologies CUMBGAP-PMH Floor Protection, Side Fuel Door Locked Shut, Both Fuel Doors Accessible