CORNER INSTALLATIONS - USA ONLY

SIDE FUEL DOOR LOCKED SHUT

 

 

52"

 

coverage

optional

optional

-5/8"

coverage

34

 

 

 

Calculating Alternate Floor Protection Material

Thermal Conductivity: k value

The k value indicates the amount of heat (in BTU’s) that will flow in 1 hour through 1 square foot of a uniform material 1 inch thick for each degree (F) of temperature difference from one side of the material to the other. The LOWER the k factor means less heat is being conducted through the non-combustible material to the combustible material beneath it. The k value of a material must be equal or smaller then the required k value to be accept- able.

52"

optionalcoverage

fuel

door

Front

 

loading

 

-5/8”

8"

38

 

16" required

8"

coverage

-3/8" 30

(BTU) (inch) (foot2 (hour) (oF)

Thermal Resistance: R value

The R value is a measure of a material’s resisteance to heat transfer. R value is convenient when more than one material is used since you can add the R values together, whereas you can not do this for k value. The HIGHER the R factor means less heat is being conducted through the non-combustible material to the combustible material beneath it. The R value of a material must be equal or larger then the required R value to be accept-

BOTH FUEL DOORS ACCESSIBLE

 

 

48-7/16"

53-7/16"

optional coverage

 

 

 

able.

Converting k to R:

Divide 1 by k and multiply the results times the thickness in inch- es of the material.

R = 1/k x inches of thickness

Converting R to k:

optional coverage

38-5/8"

44-3/4"

 

 

optional

 

coverage

Fuel loading

16"

door

 

Divide the inches of thickness by R.

k = inches of thickness/R

Calculatons:

Example: Floor protection requires k value of 0.84 and 3/4 inch thick.

Alternative material has a k value of 0.6 and is 3/4 inch thick.

 

8"

25-3/4"

 

16"

 

required coverage

 

11-1/8"

18-5/8"

 

 

 

Divide 0.6 by .75 = k value of 0.80. This k value is smaller than 0.84 and therefore is acceptable.

HORIZONTAL VENTING

NOTE: Drawings are for illustration purposes only and are not to scale.

Floor protection must extend length of flue and 2" (51mm) beyond each side of pipe (shaded area)

USA - Required

CANADA - Recommended

Page 8

7006-188E

September 1, 2008

Page 8
Image 8
Hearth and Home Technologies CUMBGAP-MBK, CUMBGAP-PMH Horizontal Venting, USA Required Canada Recommended