Hearth and Home Technologies Cyclone-Cust Finishing, A. Mantel Projections, B. Facing Material

Models: Cyclone-Cust

1 46
Download 46 pages 42.76 Kb
Page 30
Image 30
11 Finishing

11 Finishing

A. Mantel Projections

This appliance is approved to be installed with a clearance to the ceiling and/or other projections of 34-3/8 inch minimum from the top of the fireplace (see Figure 11.1).

SLIP

SECTION

FRAMING

MEMBERA. Mantel Projections COMBUSTIBLE MATERIAL

FIRESTOP

GLASS

TUBE

 

34-3/8 in.

TO CEILING

AND/OR MANTEL

TOP

41-3/8 in.

OF UNIT

(+0 to -1/2 in.)

Figure 11.1 Clearances to mantels or other combustibles above appliance

B. Facing Material

B. Facing Material WARNING

Fire Risk.

Do NOT obstruct air inlet or outlet grilles. Do NOT modify grilles.

• Modifying or covering grilles could cause temperature rise and fire hazard.

Finishing materials must not interfere with:

Air flow through grilles or louvers.

Operation of louvers or doors.

Access for service.

WARNING

Fire Risk.

Finish all edges and fronts to clearances and specifications listed in manual.

Install combustible materials only up to specified clearances on top, front and side.

Seal joints between the finished wall and appliance top and sides using only a 300º F minimum sealant.

NON-COMBUSTIBLE

COMBUSTIBLE

ON SIDES

0 IN. SEALANT MATERIAL 0 IN.

Figure 11.2 Facing Diagram

Sheetrock or other finishing materials can be brought to within 0 inches on the sides and bottom.

Finishing materials for the top of the fireplace base must be noncombustible and removable for access to controls. All clearances must be maintained (see Figure 11.3).

Ø 9-1/8 in. MIN.

OPENING

MATERIAL MUST BE

NON-COMBUSTIBLE

AND REMOVABLE

TOP MUST

MAINTAIN 1/2 in.

CLEARANCE

1/2 in.

Figure 11.3

30

Heat & Glo • Cyclone-Cust2061-900 Rev. L • 10/08

Page 30
Image 30