B. Installing Vent Components
1.Attach the First Vent Component to the Starting Collars
To attach the first vent component to the starting collars of the fireplace:
•Apply a 3/8 inch (9.5mm) bead of stove cement around the 5 inch (127mm) fireplace starting collar.
•Make sure that the fireplace rope gasket supplied with the fireplace seals between the first
•Lock the vent components into place by sliding the con- centric pipe sections with four (4) equally spaced interior beads into the fireplace collar or previously installed com- ponent end with four (4) equally spaced indented sections.
•When the internal beads of each
•The first 90° elbow installed in the vent system of a rear venting fireplace MUST BE in a vertical position.
STARTING
COLLAR
STOVE
SEALANT
BEAD
FIRST VENT
COMPONENT
1 INCH (25.4mm)
Figure 10. Attaching the First Vent Component to the Starting Collars
!WARNING: A 3/8 INCH (9.5 MM) BEAD OF STOVE CEMENT MUST BE PLACED AROUND
THE 5 INCH (127 MM) FIREPLACE STARTING COL-
LAR BEFORE ATTACHING THE FIRST VENT COM- PONENT. FAILURE TO SEAL THIS JOINT MAY CAUSE THE FIREPLACE TO OPERATE IMPROPER- LY. SEE THE DIAGRAM .
!WARNING: ENSURE THAT THE FIBER- GLASS ROPE GASKET SUPPLIED WITH
THE FIREPLACE SEALS BETWEEN THE FIRST VENT COMPONENT AND THE OUTER FIREPLACE WRAP.
If the installation is for a termination cap attached directly to the fireplace, skip to the sections, Install Firestops and Vent Termination.