For Vertical Runs - The vent system must be supported every eight (8) feet (2.4m) above the fireplace flue outlet by wall brackets.
To install support brackets for vertical runs:
•Attach wall brackets to the vent pipe and secure the wall bracket to the framing members with nails or screws.
Figure 14. Installing Support Brackets
4. Install Firestops
For Horizontal Runs - Firestops are REQUIRED on both sides of a combustible wall through which the vent passes.
NOTE: Model
To install firestops for horizontal runs that pass through either interior or exterior walls:
•Cut a
NOTE: The center of the hole is one (1) inch (25.4mm) above the center of the horizontal vent pipe.
•Position the firestops on both sides of the hole previ- ously cut and secure the firestops with nails or screws.
•The heat shields of the firestops MUST BE placed to- wards the top of the hole.
•Continue the vent run through the firestops.
12" |
(305mm) |
12" |
(305mm) |
1" (25.4 mm) |
VENT PIPE |
Figure 15. 12" x 12" Hole and Vent Pipe |
HEAT SHIELD
TRIM HEAT SHIELD IF TOO LONG, ADD TO SHIELD IF TOO SHORT
EXTERIOR
FIRESTOP
INTERIOR
FIRESTOP
Figure 16. Heat Shield, Interior & Exterior Firestops
20