Step 3. Installing the Vent System

Step 3. Installing the Vent System

A. Vent System Approvals

These models are approved to use D-series direct vent pipe components and terminations (see Figures 4 and 5). Approved vent system components are labeled for identification. This pipe is tested and listed as an approved component of the fireplace. The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall. There is no required pitch for horizontal vent runs. NO OTHER VENTING SYSTEMS OR COMPO-

NENTS MAY BE USED.

Detailed installation instructions are included with each vent termination kit and should be used in conjunction with this Installers Guide.

The flame and ember appearance may vary based on the type of fuel burned and the venting configuration used.

Identifying Vent Components

The vent systems installed on this gas fireplace may include one, two, or three 90°elbow assemblies. The relationships of vertical rise to horizontal run in vent configurations using 90° elbows MUST BE strictly adhered to. The rise to run relation- ships are shown in the venting drawings and tables. Refer to the diagrams on the next several pages.

NOTE: Two 45° elbows may be used in place of one 90° elbow. Rise to run ratios in the vent system must be followed if 45° elbows are used.

This model has vent starting collars on both the top and the back of the unit. Depending upon the installation, decide which ONE set of starting collars will be used to attach the vent system. The starting collar sealing cap must remain on the starting collar NOT used.

STRAIGHT UP

VERTICAL VENTING

V (FT.)

40' MAX. (12.4 M)

NOTE: On vertical venting configurations where the vertical component is over 10 feet, you may want to install the vertical baffle included in the manual bag assembly to improve flame appearance.

Figure 6. Straight Up Vertical Venting

 

 

 

Vent system components

Terminations Kits

VERTICAL

 

 

 

 

 

 

 

 

TERMINATION

 

STORM COLLAR

 

 

 

 

 

 

 

 

ROOF FLASHING

DVK-01D

DVK-TVCD

HORIZONTAL

 

HORIZONTAL PIPE

TERMINATION

 

 

SUPPORT

 

 

 

 

 

 

 

 

PIPE LENGTH

DVK-01TRD

 

 

 

 

 

WALL FIRESTOP

 

 

 

 

90 DEGREE

CEILING

WALL BRACKET

 

 

FIRESTOP

 

 

 

ELBOW

 

 

Figure 5. Vent System Components and Termination Kits

 

 

 

 

14

 

 

Page 14
Image 14
Heat & Glo LifeStyle 7000XLT Installing the Vent System, A. Vent System Approvals, Nents May Be Used, Terminations Kits