J. Chimney Termination Requirements

J. Chimney Termination Requirements

Install a cap approved and listed for this fireplace system.

Locate cap where it will not become plugged by snow or other materials.

Locate cap away from trees or other structures.

The bottom of the termination cap must be at least 3 ft (.91 m) above the roof AND at least 2 ft (.61 m) above any portion of roof within 10 ft (3.05 m) as shown in Figure 8.10.

The distance required between caps is shown in Figure 8.10.

Slanted Roofs

Chimney must extend 3 ft (.9 m) above the roof

Flat Roofs

Chimney must extend 3 ft (.9 m) above the roof

Chimney must extend 2 ft (.6 m) above any portion of the roof or adjacent structures within

10 ft (3 m) of the chimney

Chimney must extend 2 ft (.6 m) above any portion of the roof or adjacent structures within

10 ft (3 m) of the chimney

Termination Requirements

Gas, Wood or Fuel

Gas, Wood or Fuel

Oil Termination

Oil Termination

 

See

 

A

illustration

 

18 in.

above for wood

See

(457 mm)

 

B

 

illustration

Wood

above for wood

 

20 in. min. *

 

Gas

(508 mm)

Gas

Fuel Oil

 

Termination

Termination

 

 

Termination Caps Staggered Height

Termination Caps Same Height

 

 

 

* If using decorative cap cover(s), this distance may

A

Gas Termination

Wood or Fuel Oil Termination

need to be increased. Refer to the installation instruc-

B

6 in. (152 mm) min.

20 in. (508 mm) min.

tions supplied with the decorative cap cover.

 

 

 

Multiple Chimney Locations

Figure 8.10 Multiple Chimney Locations

30

Heat & Glo • EM-415, EM-485 • 33056 • Rev V • 05/08

Page 30
Image 30
Heat & Glo LifeStyle EM-415H, EM-485TH owner manual J. Chimney Termination Requirements