Heat & Glo LifeStyle ST-42TVFL-IPI C. Bedroom Installation in Canada, D. Vent Termination

Models: ST-42TVFL-IPI

1 27
Download 27 pages 62.54 Kb
Page 15
Image 15
C. Bedroom Installation in Canada

C. Bedroom Installation in Canada

This model MUST NOT be vented into a vent system installed exterior to a building. The part of the vent system above the roof line can be exterior to the building.

D. Vent Termination

WARNING: MAJOR U.S. BUILDING ! CODES SPECIFY MINIMUM

CHIMNEY AND/OR VENT HEIGHT ABOVE THE ROOF TOP. THESE MINIMUM HEIGHTS ARE NECESSARY IN THE INTEREST OF SAFETY. FIGURE 7 AND TABLE SHOW MINIMUM HEIGHTS, PROVIDED THE TERMINATION CAP IS AT LEAST 8-FEET FROM A VERTICAL WALL.

NOTE: THERE SHOULD BE A 5 FOOT (60”)

MINIMUM CLEARANCE TO AN UNVENTILATED VINYL CLAD SOFFIT.

VENT CAP

LOWEST DISCHARGE OPENING

X

12

ROOF PITCH IS X/12

H(MIN.)-MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING

ROOF PITCH

H (MIN.) FT.

FLAT TO 6/12

1.0

OVER 6/12 TO 7/12

1.25

OVER 7/12 TO 8/12

1.5

OVER 8/12 TO 9/12

2.0

OVER 9/12 TO 10/12

2.5

OVER 10/12 TO 11/12

3.25

OVER 11/12 TO 12/12

4.0

OVER 12/12 TO 14/12

5.0

OVER 14/12 TO 16/12

6.0

OVER 16/12 TO 18/12

7.0

OVER 18/12 TO 20/12

7.5

OVER 20/12 TO 21/12

8.0

Figure 7. Vent Termination

15

Heat & Glo • ST-42TVFL-IPI455-902 Rev. C • 12/07

Page 15
Image 15
Heat & Glo LifeStyle ST-42TVFL-IPI owner manual C. Bedroom Installation in Canada, D. Vent Termination