Heat Controller A-13 installation instructions D. Adjusting Or Checking Furnace Input

Models: A-13

1 56
Download 56 pages 46.58 Kb
Page 15
Image 15
D. ADJUSTING OR CHECKING FURNACE INPUT

FIGURE 14

FIGURE 15

MANIFOLD PIPE

D. ADJUSTING OR CHECKING FURNACE INPUT

Natural Gas Line Pressure 5- 10.5W.C.

LP Gas Line Pressure 11- 13W.C.

Natural Gas Manifold Pressure 3.5W.C

LP Gas Manifold Pressure - 10W.C.

Supply and manifold pressure taps are located on the gas valve body 1/8N.P.T. and on the manifold.

Use a properly calibrated manometer gauge for accurate gas pressure readings.

Only small variations in the gas flow should be made by means of the pressure regulator adjustment. Furnaces functioning on LP gas must be set by means of the tank or branch supply regulators. The furnace manifold pressure should be set at 10W.C. at the gas con- trol valve.

To adjust the pressure regulator, remove the regulator cap and turn the adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. Then replace

the regulator cap securely.

Any necessary major changes in the gas flow rate should be made by changing the size of the burner orifices. To change orifice spuds, shut off the manual main gas valve and remove the gas manifold.

For elevations up to 2,000 feet, rating plate input ratings apply. For high altitudes (elevations over 2,000 ft.), see conversion kit index 92-21519-XX for derating and orifice spud sizes.

Check of input is important to prevent over-firing of the furnace beyond its design- rated input. NEVER SET INPUT ABOVE THAT SHOWN ON THE RATING PLATE. Use the following table or formula to determine input rate.

Cu. Ft. Per Hr. Required =

Heating Value of Gas (BTU/Cu. Ft.) x 3600

Time in Seconds (for 1 Cu. Ft.) of Gas

Start the furnace and measure the time required to burn one cubic foot of gas. Prior to checking the furnace input, make certain that all other gas appliances are shut off, with the exception of pilot burners. Time the meter with only the furnace in operation.

IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000 FEET (610 METERS): The main burner orifices in your furnace and in these kits are sized for the nameplate input and intended for installations at elevations up to 2,000 feet in the USA or Canada, or for ele- vations of 2,000 - 4,500 feet (610 -1,373 meters) in Canada if the unit has been derated at the factory. For elevations above 2,000 feet (610 meters) IN THE USA ONLY (see ANSI-Z223.1), the burner orifices must be sized to reduce the input 4% for each 1,000 feet (305 meters) above sea level.

15

Page 15
Image 15
Heat Controller A-13 installation instructions D. Adjusting Or Checking Furnace Input